Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/28/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The applicable codes for the project are the 2018 editions of the International Code and the 2017 National Electric Code. Revise the Applicable Code information on sheet T1.0, the Energy Conservation Info on sheet A1.0, and item 1 of the Mechanical Notes on sheet ME to indicate the correct codes for this project. 2. Demonstrate energy code compliance for the addition to the building envelope using calculations based on the current code. Reference: Section C502.1, International Energy Conservation Code 2018. 3. Show that the specified heat pump for the addition complies with the requirements of Section C403, IECC 2018. Reference: Section C502.2.3, IECC 2018. 4. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018. 5. Provide calculations to verify that adequate ventilation will be provided for the addition. Reference: Section 403.3.1.1, IMC 2018. 6. Provide locking access port caps for the condensing units per Section 1101.10, IMC 2018 or locate the condensing unit in a controlled space. |
01/28/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide calculations to show that the size of the overflow scupper has a drainage capacity equal to that of the primary scupper. Reference: Sections 1106.5 and 1108.3, IPC 2018. |
01/28/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
02/08/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
02/09/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
02/10/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM00531 665 N Swan Rd Office Expansion TRANSMITTAL: February 10, 2021 This site is located in the O-3 zone (UDC 4.7.15). Administrative and Professional Office is a permitted use in this zone (Table 4.8-4) Subject to Use Specific Standard 4.9.13.K. 1. Zoning has reviewed the building plans but cannot approve until a Development Package meeting the requirements of Administrative Manual 2-06 has been submitted and approved. Based on the expansion calculation provided on this building plan, 37% the site will need to be brought up to full code compliance to include but not limited to, vehicle & bicycle parking, pedestrian circulation, solid waste, etc. 2. Provide a copy of the last approved development package/site plan with your development package submittal. 3. Provide a copy of Rezoning case C9-75-11 with your development package submittal. If you have any questions about this transmittal, please contact Elisa Hamblin, (520) 837-4966 or Elisa.Hamblin @tucsonaz.gov |
02/16/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet S1.0; General Framing Notes/General Foundation Notes: Please revise all references to the 2012 IBC. 2. General: Please provide structural calculations for the addition framing and foundation. 3. General: Please provide a Special Inspections Certificate with Parts A and B completed. 4. General: Please provide written responses to all review comments. |
02/16/2021 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Reqs Change | |
02/18/2021 | SBLOOD1 | ENGINEERING | REVIEW | Reqs Change | See zoning comments about the need of a development package approved before approving the building plans. Stephen Blood (520) 837-4958 Stephen.blood@tucsonaz.gov |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/22/2021 | PCAMARE1 | OUT TO CUSTOMER | Completed |