The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T21CM00368
Parcel: 12208016B

Address:
4112 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM00368
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed Clarify the new 4" waste line running east-west on the right-of-way north of the new building wall. Nothing is shown on the architectural site plan to explain its ultimate purpose, any required easements, or any future connections. Reference: Section 107.2.1, IBC 2018.
01/26/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed Demonstrate energy code compliance for the alteration to the building envelope (e.g. new wall, windows, etc.) using calculations based on the current code. Reference: Sections C503.1 and C503.3, International Energy Conservation Code 2018.
01/26/2021 ROBERT SHERRY WATER REVIEW Passed Show the locations and sizes of the water meter and backflow preventer on the site plan. Reference: Section 107.2.1, IBC 2018.
02/01/2021 JPEELDA1 FIRE REVIEW Approved
02/02/2021 STEVE SHIELDS ZONING REVIEW Passed
02/02/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/03/2021 PCAMARE1 ENGINEERING REVIEW Passed
02/10/2021 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Completed
02/10/2021 EHAMBLI1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed