Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM00368
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/26/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | Clarify the new 4" waste line running east-west on the right-of-way north of the new building wall. Nothing is shown on the architectural site plan to explain its ultimate purpose, any required easements, or any future connections. Reference: Section 107.2.1, IBC 2018. |
| 01/26/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | Demonstrate energy code compliance for the alteration to the building envelope (e.g. new wall, windows, etc.) using calculations based on the current code. Reference: Sections C503.1 and C503.3, International Energy Conservation Code 2018. |
| 01/26/2021 | ROBERT SHERRY | WATER | REVIEW | Passed | Show the locations and sizes of the water meter and backflow preventer on the site plan. Reference: Section 107.2.1, IBC 2018. |
| 02/01/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 02/02/2021 | STEVE SHIELDS | ZONING | REVIEW | Passed | |
| 02/02/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/03/2021 | PCAMARE1 | ENGINEERING | REVIEW | Passed | |
| 02/10/2021 | CLAYTON TREVILLYAN | BUILDING-COMMERCIAL | REVIEW | Completed | |
| 02/10/2021 | EHAMBLI1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |