Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM00360
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/15/2021 | DTRAMME1 | ENGINEERING | REVIEW | Passed | |
| 01/26/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 01/28/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 02/04/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 02/04/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide complete compliance with the 2018 IECC for the lighting. 2. Provide a note on the power plan requiring compliance with NEC 517.13 for the wiring methods. 3. Provide for Tamper Resistant Receptacles per NEC 406.12 where applicable. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
| 02/04/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet 3G01.02; Code Review Data (Occupant Load): A note indicates to refer to G02.01 for individual space occupancy loads. It does not appear those occupant loads are indicated on 3G02.01. Please verify. 2. Sheet 3G01.02; Code Review Data: Please indicate the total occupant load per floor on this sheet. In addition, indicate the occupant load and calculations for means of egress required/provided, and the plumbing fixture calculations required/provided. 3. General: Please provide north arrows on all plans. 4. General: Please provide written responses for all review comments. |
| 02/04/2021 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/08/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | . |
| 03/04/2021 | JPEELDA1 | FIRE | REVIEW | Approved |