Permit Number: T21CM00360
Parcel: 13608032E

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM00360
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/15/2021 DTRAMME1 ENGINEERING REVIEW Passed
01/26/2021 ROBERT SHERRY WATER REVIEW Completed
01/28/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
02/04/2021 STEVE SHIELDS ZONING REVIEW Approved
02/04/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide complete compliance with the 2018 IECC for the lighting.
2. Provide a note on the power plan requiring compliance with NEC 517.13 for the wiring methods.
3. Provide for Tamper Resistant Receptacles per NEC 406.12 where applicable.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
02/04/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet 3G01.02; Code Review Data (Occupant Load): A note indicates to refer to G02.01 for individual space occupancy loads. It does not appear those occupant loads are indicated on 3G02.01. Please verify.
2. Sheet 3G01.02; Code Review Data: Please indicate the total occupant load per floor on this sheet. In addition, indicate the occupant load and calculations for means of egress required/provided, and the plumbing fixture calculations required/provided.
3. General: Please provide north arrows on all plans.
4. General: Please provide written responses for all review comments.
02/04/2021 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/08/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed .
03/04/2021 JPEELDA1 FIRE REVIEW Approved