Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM00353
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/19/2021 | DTRAMME1 | ENGINEERING | REVIEW | Passed | |
| 01/26/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide metering faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 2. Provide the number of drinking fountains that complies with the requirements of Sections 2902.1and 2902.5, IBC 2018 and Section 410.3, IPC 2018. (The plans show a code-compliant dual-height drinking fountain but the plumbing fixture schedule specifies a single level drinking fountain.) 3. Revise detail 2/P2 to show the specified vacuum relief valve for the water heater installed per the manufacturer's listing information, i.e. with no valves located between the vacuum relief valve and the water heater. Reference: Sections 303.2 and 504.2, IPC 2018. 4. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018. 5. Provide a cleanout for the section of 3" horizontal drain located immediately downstream of the drinking fountain. Reference: Section 708.1.1, IPC 2018. |
| 01/26/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide a reference copy of the Landlord's mechanical plans. Reference: Section 107.2.1, IBC 2018. 2. Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). The exhausted air from the restrooms shall be limited to no more than 10% of any subsequent supply air stream. Reference: Section 403.2.1 (4), IMC 2018. |
| 01/26/2021 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 02/03/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Ref; Plan Sheet E4. The Keyed Note # 3 states the panel A to be installed by Contr. However the panel schedule shows the panel as existing. Please clarify. 2. Provide complete compliance with the 2018 IECC for the lighting. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting Code (OLC). |
| 02/04/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 02/04/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/04/2021 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/22/2021 | JPEELDA1 | FIRE | REVIEW | Approved |