Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM00350
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/05/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The detail still includes portions of the recirculation piping (e.g. the circuit setter) but the cold water shut off valve is missing. [Second comment: The water heater detail shows a hot water recirculation loop but the plan shows no hot water distribution piping. Revise the detail to match the plans (i.e. why is an under-counter water heater mounted on a cantilevered shelf). Show the route and termination of the pan drain.] [Initial comment: Provide a detail of the 25-gallon water heater installation, including the excess pressure relief, expansion tank, vacuum relief or other anti-siphon device, safety pan, and valves. Reference: Sections 503.1, 504, 606.1, and 607.3, IPC 2018.] 2. As specified, WH-2 is not an instantaneous water heater but a storage type water heater. The electric water heater detail will essentially apply to both WH-1 and WH-2 with regard to T&P relief valve, shut off valve, and the expansion tank. |
| 08/05/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 08/18/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM00350 651 W Roger Rd Convert residence to commercial use TRANSMITTAL: August 18, 2021 This site is located in the I-1 zone (UDC 4.7.29). An administrative office is a permitted use in this zone (Table 4.8-5) Subject to Use-Specific Standards 4.9.13.Q. Until DP21-0183 is approved Zoning cannot approve the building plan. If you have any questions about this transmittal, please contact Elisa Hamblin, Elisa.Hamblin @tucsonaz.gov |
| 08/18/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |