Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM00350
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/15/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Comment not addressed. [Initial comment: Provide information on the sequence of operation for the restroom exhaust fan to show that all of the air supplied to the restrooms will be exhausted. The exhausted air from the restrooms shall be limited to no more than 10% of any subsequent supply air stream. Reference: Section 403.2.1 (4), IMC 2018.] 2. Comment not addressed. [Initial comment: Provide exhaust for the range located in the break room. Reference: Section 505.6, IMC 2018 and Table 403.3.1.1, foot note f, IMC 2018.] |
| 07/15/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. The specification for WH-1 is a copy of the sink (P-3) specification. [Initial comment: Provide specifications for the two water heaters. Reference: Section 107.2.1, IBC 2018.] 2. Comment not addressed. [Initial comment: Provide tempered water for the restroom lavatory using an approved device conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018.] 3. The water heater detail shows a hot water recirculation loop but the plan shows no hot water distribution piping. Revise the detail to match the plans (i.e. why is an under-counter water heater mounted on a cantilevered shelf). Show the route and termination of the pan drain. [Initial comment: Provide a detail of the 25-gallon water heater installation, including the excess pressure relief, expansion tank, vacuum relief or other anti-siphon device, safety pan, and valves. Reference: Sections 503.1, 504, 606.1, and 607.3, IPC 2018.] |
| 07/22/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. Remove all references to the IRC Code in the electrical plans. Electrical should be referenced to the 2017 NEC. Verify electrical branch circuits are designated and correlate with Mechanical requirements. See Mechanical Reviewers comments. Ref; 2018 IBC sec 107.2.1, 2017 NEC. City of Tucson Commercial Plan Submittal Requirements |
| 08/02/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM00350 651 W Roger Rd Convert residence to commercial use TRANSMITTAL: August 2, 2021 This site is located in the I-1 zone (UDC 4.7.29). An administrative office is a permitted use in this zone (Table 4.8-5) Subject to Use-Specific Standards 4.9.13.Q. Until DP21-0183 is approved Zoning cannot approve the building plan. If you have any questions about this transmittal, please contact Elisa Hamblin, Elisa.Hamblin @tucsonaz.gov |