Permit Number: T21CM00350
Parcel: 10605010A

Address:
651 W ROGER RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM00350
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/15/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The specification for WH-1 is a copy of the sink (P-3) specification. [Initial comment: Provide specifications for the two water heaters. Reference: Section 107.2.1, IBC 2018.]
2. Comment not addressed. [Initial comment: Provide tempered water for the restroom lavatory using an approved device conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018.]
3. The water heater detail shows a hot water recirculation loop but the plan shows no hot water distribution piping. Revise the detail to match the plans (i.e. why is an under-counter water heater mounted on a cantilevered shelf). Show the route and termination of the pan drain. [Initial comment: Provide a detail of the 25-gallon water heater installation, including the excess pressure relief, expansion tank, vacuum relief or other anti-siphon device, safety pan, and valves. Reference: Sections 503.1, 504, 606.1, and 607.3, IPC 2018.]
07/15/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. [Initial comment: Provide information on the sequence of operation for the restroom exhaust fan to show that all of the air supplied to the restrooms will be exhausted. The exhausted air from the restrooms shall be limited to no more than 10% of any subsequent supply air stream. Reference: Section 403.2.1 (4), IMC 2018.]
2. Comment not addressed. [Initial comment: Provide exhaust for the range located in the break room. Reference: Section 505.6, IMC 2018 and Table 403.3.1.1, foot note f, IMC 2018.]
07/22/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

Remove all references to the IRC Code in the electrical plans. Electrical should be referenced to the 2017 NEC.

Verify electrical branch circuits are designated and correlate with Mechanical requirements. See Mechanical Reviewers comments.

Ref; 2018 IBC sec 107.2.1, 2017 NEC.

City of Tucson Commercial Plan Submittal Requirements
08/02/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM00350
651 W Roger Rd
Convert residence to commercial use

TRANSMITTAL: August 2, 2021
This site is located in the I-1 zone (UDC 4.7.29). An administrative office is a permitted use in this zone (Table 4.8-5) Subject to Use-Specific Standards 4.9.13.Q.

Until DP21-0183 is approved Zoning cannot approve the building plan.

If you have any questions about this transmittal, please contact Elisa Hamblin, Elisa.Hamblin @tucsonaz.gov