Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21CM00350
Parcel: 10605010A

Address:
651 W ROGER RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM00350
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2021 DTRAMME1 ENGINEERING REVIEW Passed
01/26/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Specify that all proposed plumbing fixtures (e.g. Sink, MFG TBD) shall be listed by a third-party certification agency as complying with the relevant standards. Reference: Section 303.4, IPC 2018.
2. Provide specifications for the two water heaters. Reference: Section 107.2.1, IBC 2018
3. Provide a metering faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
4. Provide tempered water for the restroom lavatory using an approved device conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018.
Provide a detail of the 25-gallon water heater installation, including the excess pressure relief, expansion tank, vacuum relief or other anti-siphon device, safety pan, and valves. Reference: Sections 503.1, 504, 606.1, and 607.3, IPC 2018.
01/26/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide specifications and listing information for the proposed Plasma Ionizer. Reference: Sections 301.7 and 301.8, IMC 2018.
2. Provide ventilation for office #100. Ventilation is required and must be provided whenever the space is occupied. Reference: Sections 401.2 and 401.3, IMC 2018.
3. Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2018.
4. Provide information on the sequence of operation for the restroom exhaust fan to show that all of the air supplied to the restrooms will be exhausted. The exhausted air from the restrooms shall be limited to no more than 10% of any subsequent supply air stream. Reference: Section 403.2.1 (4), IMC 2018.
5. Provide exhaust for the range located in the break room. Reference: Section 505.6, IMC 2018 and Table 403.3.1.1, foot note f, IMC 2018.
01/26/2021 ROBERT SHERRY WATER REVIEW Completed
02/01/2021 JPEELDA1 FIRE REVIEW Approved
02/02/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM00350
651 W Roger Rd
Convert residence to commercial use

TRANSMITTAL: February 2, 2021
This site is located in the I-1 zone (UDC 4.7.29). An administrative office is a permitted use in this zone (Table 4.8-5) Subject to Use-Specific Standards 4.9.13.Q.

Provide documentation that the entire structure was approved as a commercial use. Based on the Pima County Assessor’s information it was only a portion of the structure that was used as a commercial use. If there is no documentation a Development Package meeting Administrative Manual 2-06 will be required to be submitted and approved prior to this building plan.

If you have any questions about this transmittal, please contact Elisa Hamblin, (520) 837-4966 or Elisa.Hamblin @tucsonaz.gov
02/02/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Designate branch circuits and panels for all power devices and lighting and indicate on the electrical floor plan.
2. Provide compliance with the 2018 IECC for lighting.
Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
02/10/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/10/2021 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/18/2021 ELISA HAMBLIN ZONING_HISTORIC REVIEW Passed