Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T21CM00347
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/12/2022 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 03/14/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/15/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 03/15/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 03/15/2022 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 03/23/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 03/23/2022 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 03/23/2022 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/29/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. This project is considered commercial. Remove references to the IRC Code and replace references to correlate with the 2017 NEC. Where is the breaker panel located? If located in the bathroom or closet, please relocate to an acceptable location. NEC 240.24A thru E. Modified branch circuits to comply with NEC 210.12D New Breezeway lighting to comply with the 2012 Tucson/Pima County Outdoor Lighting Code. Verify maintenance outlets provided for the Mechanical equipment inside and roof. NEC 210.63 and 210.70A(3) where applicable. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code. |