Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM00347
Parcel: 122163660

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM00347
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/12/2022 JVINCEN1 FIRE REVIEW Approved
03/14/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/15/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
03/15/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
03/15/2022 ROBERT SHERRY WATER REVIEW Passed
03/23/2022 STEVE SHIELDS ZONING REVIEW Approved
03/23/2022 SSHIELD1 ENGINEERING REVIEW Passed
03/23/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/29/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

This project is considered commercial. Remove references to the IRC Code and replace references to correlate with the 2017 NEC.

Where is the breaker panel located? If located in the bathroom or closet, please relocate to an acceptable location. NEC 240.24A thru E.

Modified branch circuits to comply with NEC 210.12D

New Breezeway lighting to comply with the 2012 Tucson/Pima County Outdoor Lighting Code.

Verify maintenance outlets provided for the Mechanical equipment inside and roof. NEC 210.63 and 210.70A(3) where applicable.

Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements, 2012 Tucson/Pima County Outdoor Lighting Code.