Permit Number: T21CM00299
Parcel: 123071180

Address:
1220 N NORRIS AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM00299
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/27/2021 ANDREW CONNOR NPPO REVIEW Passed
01/27/2021 PCAMARE1 ENGINEERING REVIEW Passed
02/02/2021 NMARTEL1 ZONING REVIEW Reqs Change PDSD TRANSMITTAL
Nicholas Martell, Planner
T21CM00299
Residential Addition
February 02, 2021
The residential plans have been reviewed by the Zoning Review Section but cannot be approved until all zoning comments or concerns have been addressed.
1. Please submit a full floor plan of the entire residence. Zoning is unable to determine if a second full kitchen is proposed. If a full second kitchen is proposed, the property would be considered two different units, which is not permissible in the R-1 zone with a lot under 10,000 sq ft.
2. Please provide more detailed, fully dimensioned elevation drawings with the elevations and directions clearly stated.
3. The proposed setback for the new garage on the north side of the property does not meet R-1 standards. The required setback is 6' or 2/3 the height of the structure, whichever is greater. If the applicant wishes to keep the proposed setback to the north, a Design Development Option can be applied for. First, please revise the elevation drawings so zoning can determine the required setbacks.
4. 2019 Aerials show a small structure on the east end of the property that is not addressed on the submitted plans. Whether the structure is no longer in existence, being removed, or still present, please address it on the next submittal.

For reference, an example plot plan can be found here: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf

If you have any questions about this transmittal, please contact me at Nicholas.Martell@tucsonaz.gov
02/04/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change A SECOND KITCHEN REQUIRED ZONING APPROVAL.

Show yard water pipe size on site plan minimum of 1" required for added demand.

Provide Manual J report for determinimg cooling demand.
03/04/2021 LBOWERS1 ZONING_HISTORIC REVIEW Passed