Permit Number: T21CM00249
Parcel: 133360880

Address:
350 N BANFF AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T21CM00249
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/22/2021 SBLOOD1 ENGINEERING REVIEW Passed
03/25/2021 NMARTEL1 ZONING REVIEW Passed
04/08/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Show the location of the sink on the plan.

Show a receptacle outlet within 3’ of each lavatory basin in each bathroom, E3901.6. Show Bathroom receptacles on a separate 20 AMP circuit (dedicated) with outlets at no other location, E3703.4 and E3901.6.

Show at least one wall switch controlled light in bathrooms, E3903.3.

Show bathroom (without a window) exhaust fan locations with minimum 50 CFM rating and duct to the exterior, R303.3 and M1505.
04/30/2021 AWARNER1 NPPO REVIEW Passed