Permit Number: T21CM00237
Parcel: 115042480

Address:
437 E HELEN ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM00237
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/18/2021 LSHAMIS1 ZONING REVIEW Reqs Change CDRC Transmittal
Loran Shamis; Planner
Loran.Shamis@tucsonaz.gov

PROJECT: Bathroom Addition to SFR - 2nd review

Transmittal date: February 18, 2021

COMMENTS:

Address the previous reviewer's comments in a seperate letter explaining compliance as well as revise site plans.

The address on the application and the site plan do not match.

Demonstrate all setbacks from the new building addition to the property line.

More comments may be applicable in the next submittal.
03/03/2021 PCAMARE1 ENGINEERING REVIEW Reqs Change FROM: Paul Camarena
PDSD Engineering Review Section

PROJECT: T21CM00237
437 E HELEN ST


TRANSMITTAL DATE: March 3, 2021

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Engineering Review Section comments were addressed.

01. COMMENT: Engineering has reviewed the plan and cannot approve at this time. Please address the following comments.


02. COMMENT: The plan that has been submitted is not the correct plan for this address. Provide the correct plan set for this address.





If you have any questions about this transmittal, Contact Paul Camarena at Paul.Camarena@tucsonaz.gov