03/03/2022 RPARSON1 OIP REVIEW Reqs Change FROM: Robert Parsons
PDSD Residential Review Section

PROJECT: T21CM00232
Roof top Solar Panels


TRANSMITTAL DATE: March 3, 2022

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.

COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments

COMMENT: This plan set is not compliant with the Fire code. Demonstrate compliance with 2018 International Fire Code 1204.2.1.1. If the slope of the building is greater than 2:12 then compliance must be shown on the plans. Show a 36" wide access pathway from the eave to the ridge on both sides of the building. Relocate the solar panels to provide a clear fire pathway on each roof plane per 2018 IFC 1204.2.1.1 and 1204.2.1.2.

COMMENT: Residential will review the application on the next submittal

If you have any questions about this transmittal, Contact Robert Parsons any time during the week by email Robert.Parsons@Tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans