Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM00216
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/25/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Section 502.14, IMC 2018 requires the installation of source-capture exhaust for repair garages in addition to the general exhaust requirement of Section 403.3.1.1, IMC 2018. The requirement for 0.75 CFM/square foot of exhaust remains in effect. If you believe that the tire center is more like a parking garage than a repair garage, you may submit an appeal to the building official to allow the implementation of 2-level exhaust with carbon monoxide and nitrogen dioxide sensors along the lines of Section 404.1, IMC 2018 [Second comment: Provide the schedule of operation for the existing exhaust fans, EF20 and EF-21. Verify that the required make-up air for the exhaust is included in the heating/cooling load calculations.] [Initial comment: Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2018.] |