Permit Number: T21CM00216
Parcel: 132130730

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM00216
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/16/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. The COMcheck images on sheets ME-2 and ME-3 are not legible. [Initial comment: Show that the proposed replacement rooftop units meet the requirements of Sections C403.3, C403.4, and C403.5 (e.g. provide the mechanical compliance certification from COMcheck). Reference: Section C501.4, International Energy Conservation Code 2018.]
2. HVAC Load calculations on sheet ME-3 are not legible. [Initial comment: Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.]
3. Provide the schedule of operation for the existing exhaust fans, EF20 and EF-21. Verify that the required make-up air for the exhaust is included in the heating/cooling load calculations. [Initial comment: Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2018.]
03/17/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved