Permit Number: T21CM00185
Parcel: 14027042C

Address:
2622 E BILBY RD

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T21CM00185
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/22/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet S1.1; Office Framing and Foundation Plans: It does not appear that changes made at the office/restroom area on Sheet A1 have been made by the structural engineer on Sheet S1.1. Please verify and revise as required.
2. General: Please indicate in a narrative all sheets that have been revised for changes made in Delta 4. The response letter for these changes does not list all affected sheets.
3. General: Please provide written responses to all review comments.
12/01/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Cloud the changes made to the drawings as part of this revision. Reference: Section 107.2.1, IBC 2018.
2. Clarify which room is the men's restroom and which is the women's restroom (few women's restrooms have urinals).
3. Clarify the route and termination of the combustion air and vent pipes (i.e. how high is "above fl") Reference: Section 107.2.1, IBC 2018.
12/01/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Cloud the changes made to the drawings as part of this revision. Reference: Section 107.2.1, IBC 2018.
2. Clarify which room is the men's restroom and which is the women's restroom (few women's restrooms have urinals).
3. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.
12/08/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide a detailed narrative of the changes with the electrical design this re-submittal. There are delta 1's and delta 2's that don't correlate with the response letter. For example; what changes occurreed with the Outdoor Lighting?
Ref; 2018 IBC section 107.2.1, 2017 NEC

Final Status

Task End Date Reviewer's Name Type of Review Description
12/09/2021 VVERA1 OUT TO CUSTOMER Completed