Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T21CM00185
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/11/2021 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 01/21/2021 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. All plans (i.e. each sheet) shall be sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Correct the connection entry for the expansion tank in the plumbing equipment/fixture schedule to show the expansion tank connected to the cold water rather than the hot water. Reference: Section 303.2, IPC 2018. 3. Provide tempered water for the restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 419.5 and 607.1.2, IPC 2018 4. Provide a metering faucet for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds for accessibility. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 5. Provide an approved vacuum relief valve for the scheduled bottom-fed water heater that is located above the fixture outlets. Reference: Section 504.2, IPC 2018. 6. Provide calculations showing how the water supply piping has been sized. Reference: Sections 604.1 and 604.3, IPC 2018. 7. Verify that the pipe sizes called out for the flush valves will not result in water velocities greater than that recommended by the pipe manufacturer (e.g. limit the water velocity to less than 8 FPS for copper, PEX, or CPVC piping). At a minimum design flow rate of 25 GPM for a siphonic, flush-valve water closet, a 1" Type L copper pipe has a flow velocity of 9.7 FPS. Reference: Table 604.3, IPC 2018. 8. Show that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018. 9. Provide a full-open valve for the water service at the building entrance. Reference: Section 606.1(2), IPC 2018. 10. The maximum distance between cleanouts shall be 100-feet, measured along the developed pipe length. Reference: Section 708.1.1, IPC 2018. 11. An approved two-way cleanout fitting is a listed single fitting, not field-assembled as shown on detail 4/P4. Reference: Sections 707.1 (3), 708.1.3, and 708.1.8, IPC 2018 12. The controlling code for gas piping is the 2018 International Fuel Gas Code. Provide gas pipe sizing calculations demonstrating conformance to Sections 402.1 and 402.3, IFGC 2018. 13. Southwest Gas, the local gas utility, provides natural gas at 7" WG, 2 PSIG, and 5 PSIG. Appliances needing gas service at 7" WG or greater will require a gas meter that delivers at least 2 PSIG gas into a regulator located after the meter set. Reference: Section 402.1, IFGC 2018. |
| 01/21/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. All plans (i.e. each sheet) shall be sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Clarify how the unit heater flues are to be installed (e.g. flue material, slope direction, thimble requirement, condensate drain, minimum flue extension beyond the exterior wall, termination type, etc.). Reference: Section 305.1, IFGC 2018. 3. Three of the flues terminate over doorways; show how the condensate will be prevented from becoming a nuisance or hazard. Reference: Section 503.8 (4), IFGC 2018. 4. Specify the air flow rate for the evaporative coolers. Reference: Section 107.2.1, IBC 2018. 5. Demonstrate energy code compliance for the building envelope using calculations based on the current code. Reference: Sections C101.5, C103.2, C303, and C401.2, International Energy Conservation Code 2018. 6. Show how one of the "Additional Efficiency Package Options" (C406, IECC 2018) is to be accomplished. Reference: Section C401.2, IECC 2018. 7. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC unit for the offices and restroom. Reference: Section C403.1.1 and C403.3.1, IECC 2018. 8. Show that the proposed HVAC equipment for the offices and restroom meets the minimum performance requirements of Section C403.3.2, IECC 2018. 9. Provide calculations to verify that adequate ventilation will be provided for the offices and restroom. Reference: Section 403.3.1.1, IMC 2018. 10. Provide calculations to show how natural ventilation has been provided for the warehouse. Reference: Section 402.2, IMC 2018. 11. Provide information on the sequence of operation for the restroom exhaust fan, EF-1, to show that all of the air supplied to the restrooms will be exhausted. The exhausted air from the restrooms shall be limited to no more than 10% of any subsequent supply air stream. Reference: Section 403.2.1 (4), IMC 2018. 12. Provide locking access port caps for the condensing unit per Section 1101.10, IMC 2018 or locate the condensing unit in a controlled space. |
| 01/21/2021 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. Show the size and location of the proposed water meter, backflow preventer, and the water service pipe on a site plan. The development package is not a substitute for a complete site plan. Reference: Section 107.2.1 and 107.2.6, IBC 2018. 2. Verify the calculated water demand (216.1 GPM, sheet P1). Reference: Section 107.2.1, IBC 2018. 3. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf |
| 01/26/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide compliance with the current 2018 IECC for the lighting. Per the 2018 IECC Table C405.3.2(1), maximum lighting allowance for warehouses is .48 Watts per Sqf. 2. Provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code. Do not confuse the Outdoor Lighting Code with IECC. 3. Ref; Plan Sheet E6. Provide a grounding detail for the Electrical Service and building. 4. Provide complete panel schedules for panels 'P1' and 'P2'. Ref; 2018 IBC sec, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. 2012 Tucson/Pima County Outdoor Lighting Code. |
| 02/03/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet C1; Code Review Checklist (Allowable Area): Please provide the calculations on this sheet for the increase in allowable area due to frontage setback per the IBC Section 506.3.2. 2. Sheet C1; Code Review Checklist (Dead End Corridors): Per the IBC Section 1020.4 (Exception 2), a dead end corridor's maximum length is 50'. Please revise. 3. Sheet C1; Code Review Checklist: Please include the plumbing fixture calculations on this sheet. 4. Sheet A1; Interior Wall Detail A: Please indicate the interior wall stud size, gauge, etc. on this sheet. 5. General: Please provide a Special Inspections Certificate with Parts A and B completed. 6. General: Please provide written responses to all review comments. |
| 02/08/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM00185 2622 E Bilby Rd Commercial Storage TRANSMITTAL: February 8, 2021 This site is located in the I-1 zone (UDC 4.7.29). An administrative office is a permitted use in this zone (Table 4.8-5) Subject to Use-Specific Standards 4.9.13.Q. 1. Zoning has reviewed the building plans for compliance with DP20-0237 and although the building plans appear to match the DP unit the DP is approved Zoning cannot approve the building plans. If you have any questions about this transmittal, please contact Elisa Hamblin, (520) 837-4966 or Elisa.Hamblin @tucsonaz.gov |
| 03/03/2021 | SBLOOD1 | ENGINEERING | REVIEW | Reqs Change | Engineering has reviewed the building plans for compliance with DP20-0237 and although the building plans appear to match the DP unit the DP is approved Engineering cannot approve the building plans. Stephen Blood (520) 837-4958 Stephen.blood@tucsonaz.gov |
| 03/10/2021 | EHAMBLI1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/11/2021 | IMONSHI1 | OUT TO CUSTOMER | Completed |