Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM00180
Parcel: 11016221B

Address:
6255 E GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T21CM00180
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/25/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Section 502.14, IMC 2018 requires the installation of source-capture exhaust for repair garages in addition to the general exhaust requirement of Section 403.3.1.1, IMC 2018. The requirement for 0.75 CFM/square foot of exhaust remains in effect. If you believe that the tire center is more like a parking garage than a repair garage, you may submit an appeal to the building official to allow the implementation of 2-level exhaust with carbon monoxide and nitrogen dioxide sensors along the lines of Section 404.1, IMC 2018. [Initial comment: Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2018.]