03/25/2021 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Section 502.14, IMC 2018 requires the installation of source-capture exhaust for repair garages in addition to the general exhaust requirement of Section 403.3.1.1, IMC 2018. The requirement for 0.75 CFM/square foot of exhaust remains in effect. If you believe that the tire center is more like a parking garage than a repair garage, you may submit an appeal to the building official to allow the implementation of 2-level exhaust with carbon monoxide and nitrogen dioxide sensors along the lines of Section 404.1, IMC 2018. [Initial comment: Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2018.] |