Permit Number: T21CM00179
Parcel: 111052580

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM00179
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/10/2021 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Reqs Change Impact fee to be determined by Zoning.
02/10/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. General: This is a commercial project, therefore the requirements of the 2018 IBC Section 107.2 must be met. A registered design professional (architect or engineer) is required to prepare the documents and seal, sign, and date those documents. For more information, go to the City of Tucson website at www.tucsonaz.gov/PDSD.
2. General: Please provide a project valuation (labor + materials) for the tenant improvement. The fence is a separate permit (T21BU00080).
02/11/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide construction documents prepared by an Arizona Registrant (architect or engineer) that are complete and clearly indicate the extent of the proposed work. Reference: Section 107.2.1, IBC 2018.
02/11/2021 ROBERT SHERRY ELECTRICAL-COMMERCIAL REVIEW Reqs Change Provide construction documents prepared by an Arizona Registrant (architect or engineer) that are complete and clearly indicate the extent of the proposed work. Reference: Section 107.2.1, IBC 2018.
02/11/2021 SSHIELD1 ENGINEERING REVIEW Passed
02/11/2021 STEVE SHIELDS ZONING REVIEW Passed
02/11/2021 ROBERT SHERRY WATER REVIEW Reqs Change Provide construction documents prepared by an Arizona Registrant (architect or engineer) that are complete and clearly indicate the extent of the proposed work. Reference: Section 107.2.1, IBC 2018.
02/11/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide construction documents prepared by an Arizona Registrant (architect or engineer) that are complete and clearly indicate the extent of the proposed work. Reference: Section 107.2.1, IBC 2018.
02/17/2021 JVINCEN1 FIRE REVIEW Reqs Change Waiting on proper documents. See notes from bldg.