Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21CM00172
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/21/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Previous Comment: The Response Letter indicates the new canopy by Park N Shade has been engineered by Schneider Structural Engineers. No structural calculations or structural drawings for the new canopy were included in this submittal. Please provide. 2. General: When uploading the next submittal, please include all sheets (9) in the set. Include the updated sheets that replace the original review drawings. 3. General: Please provide written responses to all review comments. |
| 04/29/2021 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 05/11/2021 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 05/12/2021 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | ZONING REVIEW TRANSMITTAL FROM: PDSD Zoning Review PROJECT: T21CM00172 3939 E Broadway Blvd Covered Parking Structure w/solar TRANSMITTAL: May 12, 2021 This site is located in the C-1 zone (UDC 4.7.20). . 1. Until DP21-0090 is approved Zoning cannot approve this permit. If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov |