Permit Number: T21CM00172
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T21CM00172
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/15/2021 LOREN MAKUS ENGINEERING REVIEW Reqs Change 1. Provide a Development Package showing the proposed canopy structure.
2. Ensure the canopy edge is set back 1 foot from the PAAL or exceeds 15 feet clearance.
03/16/2021 JPEELDA1 FIRE REVIEW Approved
03/16/2021 LBOWERS1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
Electrical plan review is Denied as follows:1. Verify that the General Duty AC Disconnect Swithch is rated as "Suitable for use as Service Equipment" as required per NEC art 690.13C. 2. Provide a grounding detail for the PV racking and the steel canopys.NEC 690 Part V. Grounding and Bonding.
Ref 2017 NEC
03/16/2021 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T21CM00172
4793 S Julian Ave
Building Expansion

TRANSMITTAL: March 3, 2021
This site is located in the C-1 zone (UDC 4.7.20). .

1. As this is an commercial site and a structure, solar canopy is being added to the site a Development Package (DP), commercial site plan, meeting the requirements of the Minor Changes to Commercial/Industrial Site check list, is required. Requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/Minor_Changes_to_Commercial_Industrial_Sites_.pdf This DP will needs to be submitted and approved prior to approval of this solar plans. The required DP is a separate submittal from the building plan.

Once the DP has been submitted and approved Zoning will be able to approve this plan.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov
03/16/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet 2 of 9; Boxed Note: A note indicates "All Construction/Installation is to comply with the following: 2018 IRC". Please revise to the IBC.
2. General: Please provide structural calculations, general structural notes, details, material specifications, and sections as required at the new canopy. These require a registered design professional to seal, sign, and date all submittal documents.
3. General: On the drawings, please provide the new canopy SF, construction type, and occupancy classification.
4. General: Please provide a Special Inspections Certificate with Parts A and B completed.
5. General: Please provide written responses to all review comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/17/2021 IMONSHI1 OUT TO CUSTOMER Completed