Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T21CM00171
Parcel: 125101480

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T21CM00171
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2021 ROBERT SHERRY WATER REVIEW Completed
01/21/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
01/21/2021 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
01/26/2021 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/26/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/28/2021 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/01/2021 SSHIELD1 ENGINEERING REVIEW Passed
02/01/2021 STEVE SHIELDS ZONING REVIEW Approved
02/19/2021 JVINCEN1 FIRE REVIEW Approved