Permit Number: T21CM00150
Parcel: 13205015N

Review Status: Completed

Review Details: OTHER

Permit Number - T21CM00150
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2021 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The maximum distance between cleanouts shall be 100-feet, measured along the developed pipe length. Reference: Section 708.1.1, IPC 2018.
2. Provide a cleanout in the building sewer prior to entering the right-of-way. Reference: Pima County Standard Detail RWRD 401, 2015.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/10/2021 KROBLES1 OUT TO CUSTOMER Completed