Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T21BU00458
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/07/2021 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 10/25/2021 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet CD1.110; Demolition Plan: Please provide on this sheet the Velocity Air Building D-6 Square Footage and Construction Type. The demolition valuation will be calculated using those inputs. 2. General: The City of Tucson requires completed documentation of the treatment of asbestos by submitting a copy of the form provided by Pima County Department of Environmental Control titled Demolition/Renovation Asbestos NESHAP Exemption. Contact Pima County at 520-740-3340. |
| 10/26/2021 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 10/26/2021 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 10/26/2021 | STEVE SHIELDS | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/26/2021 | VVERA1 | OUT TO CUSTOMER | Completed |