Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T21BU00355
Parcel: 117070670

Address:
125 E 16TH ST

Review Status: Active

Review Details: WALLS - SUBMITTAL

Permit Number - T21BU00355
Review Name: WALLS - SUBMITTAL
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
07/21/2021 PCAMARE1 ENGINEERING REVIEW Passed
08/05/2021 NICHOLAS ROSS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: Nick Ross
Principal Planner

PROJECT:
T21BU00355
125 E. 16th St
Fence and Awning

TRANSMITTAL: 8/5/21
COMMENTS: the following comments are relative to an application for Historic Review (UDC 5.8.8).

This site is located in the HR-3 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6.

Fence is located within an HPZ. Historic review is required.
08/05/2021 NROSS1 NPPO REVIEW Passed
08/10/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T21BU00355
PLAN REVIEW COMMENTS
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide updated plans with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.
GENERAL REQUIREMENTS:
The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.
Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits
GENERAL COMMENTS:
1. Items built without permit may require alteration or improvement for achieving code compliance with the 2018 IRC, R105. This cannot be determined without an evaluation by a qualified professional. Complete construction plans are required for processing a building permit. The plans should show necessary structural changes for achieving building code compliance.

SITE PLAN:
1. Indicate the location of buildings and any utilities supporting the structure built without permit.

FOUNDATION PLAN:
1. Dimension the footing length, width, and depth into undisturbed soil for each footing type and condition, R403.1.1.

FRAMING PLAN:
1. Provide a complete roof framing plan with beams and rafters sized with appropriate load carrying capacity, R301.1.

SECTIONS - DETAILS:
1. Show the Post Section Detail with #4 rebar in the footing, R403.1.
2. Notate and specify the size and length of anchor bolts, R403.1.
3. Show roof (uplift resistance) fasteners (H2.5); bolt size or welds with appropriate uplift capacity, R802.11 amended.
4. Show connection at dwelling with fasteners (rafter on top plate with H2.5 or ledger with rafter hangers).
5. Show lateral support components if the carport is not attached to a building for structural stability, R802.8.

ELECTRICAL PLANS:
1. Show electrical alterations.

Please contact the plans reviewer if you have any questions:
Ken Van Karsen
520 837-4912
City of Tucson Residential Plan Review