Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T21BU00186
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/19/2021 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | Show a minimum 5' enclosure barrier per ARS 36-1681 B.1. The site plan currently shows a 4' patio wall. Remove the statement "are not required to comply with" and reolace with "in comlpiance with 305.4.2". 2018 ISPSC 305.2.1 states barrier heights and clearances shall be in accordance with all of the following: 1 through 4. These requirements are not excepted for small pools or spas with covers. The cover excludes the door/window alarm 305.4.1. |