Permit Number: T21BU00179
Parcel: 11450023B

Review Status: Completed

Review Details: WALLS

Permit Number - T21BU00179
Review Name: WALLS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/13/2021 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Provide an engineer’s calculation, design and seal for masonry partition and screen walls exceeding 7’ in height above grade on either side, IRC, R301.1.
04/23/2021 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T21BU00179
8721 E Woodland Rd.
8’ High Fence (1st Review)

TRANSMITTAL DATE: April 23, 2021

This site is located in the SR zone (UDC 4.7.4). A single-family residence is a permitted use in this zone (Table 4.8-1).

1. Per Unified Development Code (UDC) Article 6.6.2.I The maximum height of a wall or fence within a perimeter yard shall be six feet; however, the wall or fence may be higher than six feet, but no higher than ten feet, if the requirements of UDC Article 6.6.2.I.1 or .2 are met. As there are not elevations of the fence provided the requirements of UDC Article 6.6.2.I.1 or .2 cannot be verified. Unless you can meet the requirements above a Design Development Options for wall height must be submitted and approved prior to approval of this permit. DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. The DDO is a separate submittal from the building plans and is submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using the Submission Type “Zoning Administrator”.

2. Remove the reference to “Pima County” from under “CODE CHECK” as this site is not in Pima County jurisdiction.
3. The setbacks listed under “CODE CHECK” are not correct. This site does not border on a street so the 20.0’ or 1.5 X BUILDING HEIGHT, does not apply. Per UDC TABLE 6.3-1.A: DIMENSIONAL STANDARDS FOR THE RH, SR, SH, RX-1, & RX-2 ZONES, SR ZONE, Residential use to a Residential zone the minimum perimeter yard setback is 25’-0”.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov
04/23/2021 SSHIELD1 NPPO REVIEW Passed
05/10/2021 LOREN MAKUS ENGINEERING REVIEW Reqs Change The proposed fence crosses a drainage channel. Provide engineering design report demonstrating the fence will not obstruct flows for up to a 100-year event. The engineering report must address all changes to the drainage made during the construction of the fence.