Permit Number: T20RW02231
Parcel: 999999999

Address:
4405 E 3RD ST

Review Status: Completed

Review Details: ROW SWF - SUBMITTAL

Permit Number - T20RW02231
Review Name: ROW SWF - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/14/2020 JSANDER1 START START Completed
05/14/2020 PROSENB1 DOT STREET MAINTENANCE REVIEW Approved Streets irrigation does not have any comments or concerns for this location at this time. Paul Rosenboom
05/14/2020 JSANDER1 HISTORIC Review Review Comp
05/15/2020 JSANDER1 REAL_ESTATE REVIEW Needs Review
05/15/2020 CRAIG SALTZMAN DOT ENGINEERING REVIEW Reqs Change 1) Show Sight distance triangle on plan.
2) Place pole one foot behind five feet future sidewalk with two feet between back of curb and front face of sidewalk.
05/15/2020 JSANDER1 IT_NETWK REVIEW Approved
05/15/2020 JSANDER1 DOT_WATER REVIEW Needs Review
05/28/2020 JSANDER1 DOT_ELEC REVIEW Approv-Cond Approved with addition of City Streetlight J-Box and 2" conduit with bonding trace wire.