Permit Number: T20RW02194
Parcel: 999999999

Address:
4904 E BAKER ST

Review Status: Completed

Review Details: ROW SWF - SUBMITTAL

Permit Number - T20RW02194
Review Name: ROW SWF - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/14/2020 JSANDER1 START START Completed
05/14/2020 PROSENB1 DOT STREET MAINTENANCE REVIEW Approved Streets irrigation does not have any comments or concerns for this location at this time. Paul Rosenboom
05/14/2020 JSANDER1 HISTORIC Review Review Comp
05/15/2020 JSANDER1 IT_NETWK REVIEW Approved
05/18/2020 CRAIG SALTZMAN DOT ENGINEERING REVIEW Reqs Change The subject permit has been reviewed and the consultation shall address the following comments:
1) Show Sight distance triangle on plan.
2) Remove pole and meter pedestal from Sight distance triangle.
3) Remove pole and meter pedestal from future Pedestrian Access Ramp foot print ( see PAG 2015 Standard and Details).
4) Place pole one foot behind five feet future sidewalk with two feet between back of curb and front face of sidewalk.
05/18/2020 JSANDER1 REAL_ESTATE REVIEW Needs Review
05/18/2020 JSANDER1 DOT_WATER REVIEW Needs Review
05/28/2020 JSANDER1 DOT_ELEC REVIEW Approv-Cond Approved with addition of City Streetlight J-Box and 2" conduit with bonding trace wire.