Permit Review Detail
Review Status: Completed
Review Details: ROW SWF - SUBMITTAL
Permit Number - T20RW02160
Review Name: ROW SWF - SUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/14/2020 | JSANDER1 | START | START | Completed | |
05/14/2020 | JSANDER1 | IT_NETWK | REVIEW | Approved | |
05/14/2020 | PROSENB1 | DOT STREET MAINTENANCE | REVIEW | Approved | Streets irrigation does not have any comments or concerns for this location at this time. Paul Rosenboom |
05/14/2020 | JSANDER1 | HISTORIC | Review | Review Comp | |
05/15/2020 | JSANDER1 | REAL_ESTATE | REVIEW | Needs Review | |
05/15/2020 | CRAIG SALTZMAN | DOT ENGINEERING | REVIEW | Reqs Change | 1) Show Sight distance triangle on plan. 2) Remove pole and meter pedestal from Sight distance triangle. 3) Remove pole and meter pedestal from future Pedestrian Access Ramp foot print ( see PAG 2015 Standard and Details). 4) Place pole one foot behind five feet future sidewalk with two feet between back of curb and front face of sidewalk. |
05/15/2020 | JSANDER1 | DOT_WATER | REVIEW | Needs Review | |
05/28/2020 | JSANDER1 | DOT_ELEC | REVIEW | Approv-Cond | Approved with addition of City Streetlight J-Box and 2" conduit with bonding trace wire. |