Permit Number: T20RW02144
Parcel: 999999999

Address:
4414 E SENECA ST

Review Status: Completed

Review Details: ROW SWF - SUBMITTAL

Permit Number - T20RW02144
Review Name: ROW SWF - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/11/2020 JSANDER1 START START Completed
05/11/2020 JSANDER1 IT_NETWK REVIEW Approved
05/11/2020 PROSENB1 DOT STREET MAINTENANCE REVIEW Approved Streets irrigation does not have any comments or concerns for this location at this time. Paul Rosenboom
05/11/2020 JSANDER1 HISTORIC Review Review Comp
05/14/2020 ZELIN CANCHOLA DOT ENGINEERING REVIEW Reqs Change May14, 2020
T20RW02144
Verizon Cell
Zelin Canchola Transportation and Mobility Engineering

Please note the following comments:

Site address looks like 4418 E Seneca, not 4414.

The drawings and picture of proposed pole location do not match. The picture shows the pole between the sidewalk and curb, the plans show the pole is located behind the sidewalk. The preferred location is between the sidewalk and curb. Show the change to pole location between the curn and sidewalk (utility area).

Mobility control plan is acceptable.
05/20/2020 JSANDER1 DOT_ELEC REVIEW Approved
05/20/2020 JSANDER1 DOT_WATER REVIEW Approved
05/20/2020 JSANDER1 REAL_ESTATE REVIEW Needs Review