Permit Number: T20RW02093
Parcel: 999999999

Review Status: Completed

Review Details: ROW SWF - SUBMITTAL

Permit Number - T20RW02093
Review Name: ROW SWF - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/16/2020 JSANDER1 START START Completed
04/16/2020 PROSENB1 DOT STREET MAINTENANCE REVIEW Approved Streets irrigation does not have any comments or concerns for this location at this time. Paul Rosenboom
04/16/2020 JSANDER1 HISTORIC Review Approved RECOMMENDATION: Approval
04/17/2020 JSANDER1 IT_NETWK REVIEW Approved
04/20/2020 RICHARD LEIGH DOT ENGINEERING REVIEW Approved
04/20/2020 JSANDER1 DOT_WATER REVIEW Approved
05/12/2020 JSANDER1 DOT_ELEC REVIEW Reqs Change Pages LS-1 shows height of luminaire at 25'5" and on sheet A-3 new Small Cell pole luminaire height of 30'6" this is out spec; revise plan to show all lumiaire heights to be identical and to match the existing luminaire height.
Also on sheets LS-1, A-3, G-1 and PF-2 show a different mast arm on each page. Please provide a sheet showing the exact mast arm specifications to be used for this site.

Please correct the
05/12/2020 JSANDER1 REAL_ESTATE REVIEW Needs Review