Permit Number: T20RW01729
Parcel: 999999999

Review Status: Completed

Review Details: ROW SWF - SUBMITTAL

Permit Number - T20RW01729
Review Name: ROW SWF - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/20/2020 JSANDER1 START START Completed
03/20/2020 PROSENB1 DOT STREET MAINTENANCE REVIEW Approved Streets irrigation does not have any comments or concerns for this location at this time. Paul Rosenboom
03/24/2020 JSANDER1 IT_NETWK REVIEW Approved
04/01/2020 JSANDER1 HISTORIC Review Approved RECOMMENDATION: Approval
04/01/2020 JSANDER1 DOT_ELEC REVIEW Approved
04/08/2020 CRAIG SALTZMAN DOT ENGINEERING REVIEW Reqs Change 1. Show dimension to back of curb.
2. Place new pole behind future 5 Ft. sidewalk with 1 Ft. clear between back of sidewalk and new pole.
3. Traffic Control plan needs to address pedestrian traffic in the work zone.
4. Traffic control plan needs to have contact person and a cell # they can be reached at.
04/08/2020 JSANDER1 DOT_WATER REVIEW Needs Review
04/08/2020 JSANDER1 REAL_ESTATE REVIEW Needs Review