Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T20RW01679
Parcel: 999999999

Review Status: Completed

Review Details: ROW SWF - SUBMITTAL

Permit Number - T20RW01679
Review Name: ROW SWF - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/16/2020 JSANDER1 START START Completed
03/16/2020 JSANDER1 HISTORIC Review Approved RECOMMENDATION: Approval
03/18/2020 PROSENB1 DOT STREET MAINTENANCE REVIEW Approved Streets irrigation does not have any comments or concerns for this location at this time. Paul Rosenboom
03/24/2020 JSANDER1 DOT_ELEC REVIEW Reqs Change Corrections required:
1. Sheet A-3, luminaire height for City of Tucson pole is at 35’.0" and on sheet A-3.1 has the luminaire height at 30’.0" for the small cell pole. It is required for replacement poles to have street light at same height and position over the roadway as the light pole it replaces.

2. Add this text to scope of work.
REMOVE EXISTING LIGHT POLE -RETURN TO THE CITY OF TUCSON TRAFFIC MAINTENANCE ELECTRIC SHOP AT
4004 S PARK AVE, WITH A 24 HR ADVANCE NOTICE OF ARRIVAL. IF IT IS DETERMINED BY THE TM ELECTRIC SHOP INSPECTOR POLES ARE TO BE SCRAPPED, THEY WILL THEN BE TRANSPORTED BY THE CONTRACTOR TO THE HVF WEST FACILITY LOCATED AT 6581 E DREXEL RD, TUCSON, AZ AND CREDITED TO THE CITY OF TUCSON DEPT. OF TRANSPORTATION.
-OBSOLETE STREETLIGHT POLE FOUNDATIONS SHALL BE REMOVED COMPLETELY, ANY CHANGES SHALL BE AND APPROVED BY THE TRAFFIC MAINTENANCE ELECTRIC SHOP INSPECTOR IN THE FIELD.
03/25/2020 JSANDER1 IT_NETWK REVIEW Approved
03/27/2020 RICHARD LEIGH DOT ENGINEERING REVIEW Approved
03/27/2020 RLEIGH1 DOT_WATER REVIEW Approved
04/04/2020 JSANDER1 REAL_ESTATE REVIEW Needs Review