Permit Review Detail
Review Status: Completed
Review Details: ROW SWF - SUBMITTAL
Permit Number - T20RW01205
Review Name: ROW SWF - SUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/02/2020 | JSANDER1 | START | START | Completed | |
03/02/2020 | JSANDER1 | IT_NETWK | REVIEW | Completed | |
03/02/2020 | PROSENB1 | DOT STREET MAINTENANCE | REVIEW | Approved | Streets irrigation does not have any comments or concerns for this location at this time. Paul Rosenboom |
03/02/2020 | JSANDER1 | HISTORIC | Review | Approved | RECOMMENDATION: Approval |
03/09/2020 | JSANDER1 | DOT_ELEC | REVIEW | Approved | |
03/11/2020 | RICHARD LEIGH | DOT ENGINEERING | REVIEW | Reqs Change | Reviewer: Richard Leigh 520-548-5969 Richard.Leigh@tucsonaz.gov Revise drawing to indicate the placenment of sidewalk that meanders around new light pole. A 1' buffer shall be provided between the sidewalk and pole base. Or locate new light pole out of the sidewalk area. |
03/11/2020 | RLEIGH1 | DOT_WATER | REVIEW | Approved | |
03/11/2020 | JSANDER1 | REAL_ESTATE | REVIEW | Needs Review |