Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/25/2020 | JSANDER1 | START | START | Completed | |
02/25/2020 | JSANDER1 | HISTORIC | Review | Approved | RECOMMENDATION: Approval |
02/26/2020 | PROSENB1 | DOT STREET MAINTENANCE | REVIEW | Approved | Streets irrigation does not have any comments or concerns for this location at this time. Paul Rosenboom |
02/28/2020 | CRAIG SALTZMAN | DOT ENGINEERING | REVIEW | Denied | 1) Show dimension to back of curb. 2) Show site distance triangle at Bermuda St and Eastgate Dr. 3) Pole location shall be located 1 ft. behind future 5 ft. wide sidewalk with 2 ft. wide utility area between back of curb and front face of future sidewalk. 4) Pole shall not be in conflict with future PAG Std. Access Ramp at Bermuda St. and Eastgate Dr. |
03/02/2020 | JSANDER1 | DOT_ELEC | REVIEW | Approved | |
03/02/2020 | JSANDER1 | IT_NETWK | REVIEW | Approved | |
03/02/2020 | JSANDER1 | REAL_ESTATE | REVIEW | Needs Review | |
03/02/2020 | JSANDER1 | DOT_WATER | REVIEW | Needs Review |