Plan Number: T20PRE0173
Parcel: Unknown

Address:
1845 W BROWN DR

Review Status: Completed

Review Details: PREAPPLICATION LABELS

Plan Number - T20PRE0173
Review Name: PREAPPLICATION LABELS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/25/2020 ANDREW CONNOR LANDSCAPE REVIEW Completed Ensure that Zoning and Engineering comments are addressed prior to landscape section approval.
12/01/2020 GDAURIA1 COT NON-DSD FIRE Completed * Will need more information of access to lots from roadways.
* Paved fire access required to within 150' of all exterior portions of structures.
* Hydrant required to withih 400' of all exterior portions of structures (600' if sprinklered)'
12/14/2020 ZELIN CANCHOLA COT NON-DSD TRAFFIC Completed No adverse comments.

Access to lots will require a stabalized surface/dust control millings or AB treatment.
12/16/2020 ELISA HAMBLIN ZONING REVIEW Completed CDRC Thursday Pre-Submittal Transmittal
PDSD Zoning Review

FROM: Elisa Hamblin, AICP; Principal Planner

PROJECT: Thursday Pre-submittal meeting – T20PRE0173
Address: 1847 W Probasco Dr, 1845 W Brown Dr
Parcel(s): 119-41-0840, 119-41-0850, 119-41-0860, 119-41-0870, 119-41-0880
Zoning: R-1
Existing Use: Vacant
Proposed Use: Single-family residential

TRANSMITTAL DATE: December 14, 2020

COMMENTS:
1. Development must comply with the City’s Unified Development Code.
2. The proposal is to develop five existing lots, each with a single-family residence.
3. The concept generally appears to conform with zoning standards. However, exact home placement, setbacks, building height, etc. will be reviewed for conformance during the formal permit process.
4. Address all Engineering comments regarding floodplain and access/improvements.
5. Any questions or request regarding existing or future addresses should be directed to Pima County Addressing.
6. The comments provided are preliminary and are not to be assumed as a complete review of the proposal. During the formal review process, a full review will be made by Zoning to assure compliance with the applicable UDC development criteria and Technical Standards.

If you have any questions please contact me at elisa.hamblin@tucsonaz.gov.
12/16/2020 LOREN MAKUS ENGINEERING REVIEW Completed 1. Site is within FEMA SFHA Zone AE.
2. The 100-year discharge in the Ajo Wash is estimated by FEMA in the Flood Insurance Study (FIS) at 3,465 cfs. The Erosion Hazard Setback from the top of the bank of the wash is about 58.9 feet. New structures are not allowed in EHS.
3. An encroachment analysis will be required to show no increase in water surface elevation greater than 0.1 feet on any adjacent property. The analysis must address structures, fences and walls.
4. Access must be improved from Probasco or other paved roadway.
12/17/2020 SBEASLE1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Completed 200 - 230 pm - T20PRE0173 - 1847 W PROBASCO DR - Site Probasco and Mission

1. Some of these lots are more than 600' away from the nearest fire hydrant. If a new fire hydrant is needed, the existing and proposed 4" water mains are too small to supply a fire flow of 1000 gpm. Additional discussion about how these single family residents will be provided with fire protection is warranted.

2. Any questions, comments or concerns about these projects may be directed to:

Tim Rowe, P.E., Civil Engineer
Tucson Water, New Development Section
310 W. Alameda St.
P.O. Box 27210
Tucson, AZ 85726-7210
(520) 837-2106
tim.rowe@tucsonaz.gov