Plan Review Detail
Review Status: Active
Review Details: PREAPPLICATION MEETING
Plan Number - T20PRE0129
Review Name: PREAPPLICATION MEETING
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/08/2020 | GDAURIA1 | FIRE | REVIEW | Completed | * Hydrants will be required throughout so that no exterior portion of any future structure is greater than 400' travel distance from a hydrant. |
| 10/13/2020 | JOHN BEALL | M&C Public Hearing 4 Plan Amendment | Set M&C Public Hearing Date | Active | |
| 10/13/2020 | BILLIE LEE | COMMENTS | COMMENTS | Active | |
| 10/13/2020 | ELISA HAMBLIN | ZONING | REVIEW | Completed | Rezoning Pre-Submittal Transmittal FROM: Elisa Hamblin, AICP; Principal Planner PDSD Zoning Review PROJECT: Rezoning Pre-submittal meeting T20PRE0129 Address: 3131 S Portia Av Parcel(s): 13612006A Existing Zoning: SR Proposed Zoning: R-1 Existing Use: Vacant Proposed Use: Flexible Lot Development TRANSMITTAL DATE: October 13, 2020 COMMENTS: 1. Relevant rezoning or annexation conditions: C9-76-21 Original City Zoning 2. Development must comply with the Administrative Manual Section 2-06 - Development Package. 3. Development standards: per FLD standards 50% site coverage, 5.14 units/acre, 25 ft height 4. Proposed use and use-specific standards: Flexible Lot Development, UDC Article 8.7.3 5. Perimeter yard setbacks: interior – per adopted building code, boundary lots – per underlying zoning – R-1 to R-1 would require setbacks of 6 ft or 2/3 wall height 6. Applicable street setbacks: per developing area setbacks, UDC Article 6.4.5.C.2. 7. Parking requirements: 2.25 per housing unit, visitor parking may be provided on street assuming adequate street width is provided 8. Landscape requirements can be discussed further with Andy Connor at andrew.connor@tucsonaz.gov or 520-837-4950. 9. Additional comments: Development standards appear to be met at a conceptual level. 10. The comments provided are preliminary and are not to be assumed as a complete review of the proposal. During the Development Package review process, a full review will be made by Zoning to assure compliance with the applicable UDC development criteria and Technical Standards. If you have any questions please contact me at elisa.hamblin@tucsonaz.gov or (520) 837-4966. |
| 10/14/2020 | LOREN MAKUS | ELECTRICAL ENGINEERING | REVIEW | Completed | 1. Development of the site shall be in accordance with balanced basin criteria. Each drainage area and discharge location must meet balanced basin criteria. 2. The discharges from Falcon Point subdivision must be analyzed and accepted by this project. Appropriate drainage easements must be provided. |