Plan Number: T20PRE0109
Parcel: Unknown

Address:
2525 N TREAT AV

Review Status: Active

Review Details: PREAPPLICATION

Plan Number - T20PRE0109
Review Name: PREAPPLICATION
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2020 BILLIE LEE COMMENTS COMMENTS Active
09/01/2020 ANY URBAN PLANNING REVIEW Active
09/01/2020 ANY ELECTRICAL ENGINEERING REVIEW Active
09/01/2020 ELISA HAMBLIN ZONING REVIEW Completed Rezoning Pre-Submittal Transmittal

FROM: Elisa Hamblin, AICP; Principal Planner
PDSD Zoning Review

PROJECT: Rezoning Pre-submittal meeting T20PRE0109
Address: 2525 N Treat Av
Parcel(s): 112071060
Existing Zoning: R-2
Proposed Zoning: R-2 (Special Exception)
Existing Use: Utilities – Distribution System
Proposed Use: (same)

TRANSMITTAL DATE: September 1, 2020

COMMENTS:
1. Development must comply with the Administrative Manual Section 2-06 - Development Package.
2. Development standards: height, lot size, etc
3. Proposed use and use-specific standards: Distribution System, subject to 4.9.11.A.1, .2, .5, .8, .9, .11, see below.
1. The setback of the facility, including walls or equipment, shall be 20 feet from any adjacent residential zone.
2. Where a facility is not enclosed within a building, the surrounding screen shall be used as the building wall for the purposes of setbacks.
5. The use shall not have any service or storage yards.
8. Any building housing such facility shall be in keeping with the character of the zone in which it is located. The Design Review Board (DRB) shall review all applications and make recommendations to the Zoning Examiner. The DRB shall review architectural style, building elevations, materials on exterior facades, color schemes, new mechanical equipment locations, lighting of outdoor areas, window locations and types, screening, landscaping, vehicular use areas, and other contributing design features.
9. The use shall be located wholly within an enclosed building or within an area enclosed on all sides with a masonry wall or compact evergreen hedge, not less than six feet, nor more than ten feet, in height.
11. The use shall be limited to water pumping and storage facilities, telephone exchanges, and power substations with an input voltage of no greater than 138 kilovolts.
4. Perimeter yard setbacks: 10 ft or ¾ wall height
5. Applicable street setbacks: 20 ft or 1.5 times wall height on one street, 10 ft on the other street
6. Parking requirements: 2 spaces per facility
7. Landscape requirements can be discussed further with Andy Connor at andrew.connor@tucsonaz.gov or 520-837-4950.
8. Additional comments: My primary concerns relate to the use-specific standards and how they can be met with this proposal. We can discuss further at the meeting.
9. The comments provided are preliminary and are not to be assumed as a complete review of the proposal. During the Development Package review process, a full review will be made by Zoning to assure compliance with the applicable UDC development criteria and Technical Standards.

If you have any questions please contact me at elisa.hamblin@tucsonaz.gov or (520) 837-4966.
09/08/2020 GDAURIA1 FIRE REVIEW Completed