Plan Number: T20PRE0022
Parcel: Unknown

Address:
5502 E 22ND ST

Review Status: Completed

Review Details: PRESUBMITTAL MTG

Plan Number - T20PRE0022
Review Name: PRESUBMITTAL MTG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/29/2020 ANDREW CONNOR LANDSCAPE REVIEW Completed Street Landscape Borders

Located on Site
Street landscape borders must be located entirely on site, except that, if approved by the City Engineer or designee, up to five feet of the required ten foot width may be placed within the adjacent right-of-way area or within the Major Streets and Routes (MS&R) right-of-way area on MS&R streets.

Obtain permission for use of the ROW.
01/31/2020 ZELIN CANCHOLA COT NON-DSD TRAFFIC Completed January 31, 2020
T20PRE0022
Zelin Canchola Transportation

No Adverse comments. Standard requirements will apply for development Package.
01/31/2020 SBEASLE1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Completed 210 pm - T20PRE0022 - 5502 E 22ND ST - SITE Shell building
" Water is delivered to the existing building at this location via a 1" water meter from a 6" water main in 22nd St.
" If a larger water meter is necessary, please contact Ray Munoz at 837-2207 in the Tucson Water New Services Section to discuss:
o The number of water service lines, water meters, and meter sizes, necessary to serve this development.
o The advantages and disadvantages of installing the necessary water meters via Tucson Water's Job Order Contract (JOC) process.

Tim Rowe, Sr. Engineeering Associate
Tucson Water, New Development Unit
310 W. Alameda St, Tucson, AZ 85701, (520) 837-2106
01/31/2020 GDAURIA1 COT NON-DSD FIRE Completed
02/04/2020 LOREN MAKUS ENGINEERING REVIEW Completed T20PRE0022 - 5502 E 22nd St
1. Not in floodplain. Not balanced or critical.
2. Maximize water harvesting in landscape areas.
3. Sidewalk is in poor repair. Provide minimum 6-foot sidewalks along both street frontages.
02/05/2020 ELISA HAMBLIN ZONING REVIEW Completed CDRC Thursday Pre-Submittal Transmittal
PDSD Zoning Review

FROM: Elisa Hamblin, AICP; Principal Planner

PROJECT: Thursday Pre-submittal meeting - T20PRE0022
Address: 5502 E 22nd St
Parcel(s): 131100330
Zoning: C-1
Existing Use: General Merchandise Sales (Vacant)
Proposed Use: Food Service

TRANSMITTAL DATE: February 5, 2020 (REVISED)

COMMENTS:
1. Development must comply with the Administrative Manual Section 2-06 - Development Package.
2. The proposal is to demo a vacant gas station and develop the site with a drive-through restaurant. Food Service, Excluding Soup Kitchen is a permitted use in the C-1 zone subject to use-specific standards 4.9.4.M.1 & 5 and 4.9.13.O. Please note, the C-1 limits food service to one drive-through lane.
3. Development standards, such as height, parking, pedestrian access and setbacks, appear to be met with the proposal.
4. REVISION: Based on the plan brought to the meeting, adequate parking has not been provided. Parking reductions can be requested through an Individual Parking Plan.
5. The comments provided are preliminary and are not to be assumed as a complete review of the proposal. During the Development Package review process, a full review will be made by Zoning to assure compliance with the applicable UDC development criteria and Technical Standards.

If you have any questions please contact me at elisa.hamblin@tucsonaz.gov or (520) 837-4966.