Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Plan Number: T20PRE0008
Parcel: Unknown

Review Status: Completed

Review Details: PREAPPLICATION

Plan Number - T20PRE0008
Review Name: PREAPPLICATION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2020 ELISA HAMBLIN ZONING REVIEW Completed CDRC Thursday Pre-Submittal Transmittal
PDSD Zoning Review

FROM: Elisa Hamblin, AICP; Principal Planner

PROJECT: Thursday Pre-submittal meeting - T20PRE0008
Address: 2695 N Craycroft Rd
Parcel(s): 11012091A
Zoning: PAD-16
Existing Use: Medical Service - Major
Proposed Use: Medical Service - Major (expansion)

TRANSMITTAL DATE:

COMMENTS:
1. Development must comply with the Administrative Manual Section 2-06 - Development Package.
2. The proposal is for an addition to an existing Medical Service - Major use. The use is permitted per the PAD. Ensure development standards as outlined in the PAD document are met with the proposed development.
3. Additional information is needed regarding the amount of total expansion to determine applicable standards.
4. Per the PAD, building height in this area is limited to 40-60 ft.
5. The TMC Architectural Review Board shall provide a letter of recommendation to the City at the time of plan submittal advising whether the architectural design conforms to the TMC Design Guidelines.
6. The comments provided are preliminary and are not to be assumed as a complete review of the proposal. During the Development Package review process, a full review will be made by Zoning to assure compliance with the applicable UDC development criteria and Technical Standards.

If you have any questions please contact me at elisa.hamblin@tucsonaz.gov or (520) 837-4966.
01/14/2020 ANDREW CONNOR LANDSCAPE REVIEW Completed Indicate graphically, where possible, compliance with conditions PAD-16 document.
01/15/2020 LOREN MAKUS ENGINEERING REVIEW Completed 1. Clarify extent of new impervious areas on the site. If the increase is substantial, additional retention will be required.
2. Maximize water harvesting for all new landscape areas.
01/21/2020 ZELIN CANCHOLA COT NON-DSD TRAFFIC Completed * Applicant requesting Pre-action system in new wing and related areas.
* Verify that existing 4" fire riser is adequate for fire sprinkler system. They may just pull the riser from water line to the north.
* FDC to new wing to be on north end off wing.
* Hydrant located off north drive.
01/21/2020 ZELIN CANCHOLA COT NON-DSD TRAFFIC Completed No adverse comments or requirements for woek in the right of way.
01/31/2020 GDAURIA1 COT NON-DSD FIRE Completed * Applicant requesting Pre-action system in new wing and related areas.
* Verify that existing 4" fire riser is adequate for fire sprinkler system. They may just pull the riser from water line to the north.
* FDC to new wing to be on north end off wing.
* Hydrant located off north drive.
12/24/2020 SBEASLE1 TUCSON WATER NEW AREA DEVELOPMENT REVIEW Needs Review