Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2021 GARY WITTWER DOT LANDSCAPE REVIEW Approved
01/12/2021 RLEIGH1 UTILITY CLEARANCES COT STREETS DIVISION Needs Review
01/12/2021 ZELIN CANCHOLA DOT TRAFFIC REVIEW Reqs Change Provide street and stop signs per the Pima County and City of Tucson 2020 Signing and Pavement Marking Manual, which can be found at https://webcms.pima.gov/UserFiles/Servers/Server_6/File/Government/Transportation/Roadway%20Design/FINAL_PimaCounty_CityofTucson_SigningPavementMarkingManual2020_FirstEdition.pdf
01/12/2021 RICHARD LEIGH PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Completed Please submit utility notification receipts. A list of utility companies that need to be notified of the proposed improvements in the public right-of-way at the following link.

https://www.tucsonaz.gov/files/transportation/UTLAWAREMEM_rev2019Mar27z.pdf
01/12/2021 JIM FEMLING DOT STREET MAINTENANCE REVIEW Approved
01/12/2021 ERNIE ENCINAS DOT_ELEC REVIEW Approved
01/12/2021 RICHARD LEIGH DOT ENGINEERING REVIEW Reqs Change January 11, 2020

SUBJECT: La Estancia Phase II, Parcel 4 Paving Plans

PROJECT REVIEWER: Richard Leigh, DTM Eng. Review

RESUBMITTAL REQUIRED: TDOT Permit Review Section has reviewed the subject PIA paving plan and does not recommend approval at this time. The following comments need to be addressed and plans revised prior to resubmittal. Please include a response letter addressing the following comments.


1. Add the plan number "I-2020-026" in the title block of each sheet.

2. Add PIA activity number "T20PI00024" on coversheet.

3. Sheet 2: Paving Note 5 to indicate that the asphaltic concrete shall conform to PAG's Replacement Specification for Section 406 Asphaltic Concrete, dated December 12, 2019.

4. Sheet 2 through 11: Use current DTM title blocks. See Engineering Plan Template at: https://www.tucsonaz.gov/files/transportation/Engineering_Plan_Templates_Dec_2019.pdf

5. Sheets 3: Revise scupper detail to indicate placement of barricade railing along the back of the scupper.

6. Sheets 3: Verify the data provided in the Scupper Information Table, revise as necessary.

7. Sheets 5: Curb access ramps will have to be provided at the intersection of Paseo Del Fado and Camino Estrania. Refer to COT TSM Section 10-01.3.3.E

8. Sheets 5: Curb access ramps will have to be provided at the intersection of Paseo Del Fado and Camino Rebina. Refer to COT TSM Section 10-01.3.3.E

9. Sheet 10: Verify that the proposed storm drain system is based on the approved drainage report (DR) for the project. The DR calls for Type 5 catch basins while the paving plans propose Type 4 catch basins. Revise as necessary. Additionally, provide complete details for the proposed manholes and catch basins, included stationing and offsets based on paving plan, inverts, catch basin grate type, and catch basin wing lengths.

10. Provide street and stop signs per the Pima County and City of Tucson 2020 Signing and Pavement Marking Manual, which can be found at https://webcms.pima.gov/UserFiles/Servers/Server_6/File/Government/Transportation/Roadway%20Design/FINAL_PimaCounty_CityofTucson_SigningPavementMarkingManual2020_FirstEdition.pdf

11. Refer to redline drawings for additional comments and comment details.

If you have any questions, I can be reached at 520-237-8692 or emailed at Richard.Leigh@tucsonaz.gov.
01/12/2021 RICHARD LEIGH PIA COORDINATOR OUT TO CUSTOMER Completed Please submit utility notification receipts. A list of utility companies that need to be notified of the proposed improvements in the public right-of-way at the following link.

https://www.tucsonaz.gov/files/transportation/UTLAWAREMEM_rev2019Mar27z.pdf
01/12/2021 RLEIGH1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Needs Review
01/12/2021 RLEIGH1 UTILITY CLEARANCES PC WASTEWATER MGMT Needs Review
01/12/2021 RLEIGH1 UTILITY CLEARANCES QUEST COMMUNICATION Needs Review
01/12/2021 RLEIGH1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Needs Review
01/12/2021 RLEIGH1 UTILITY CLEARANCES COX COMMUNICATION Needs Review
01/12/2021 RLEIGH1 UTILITY CLEARANCES SOUTHWEST GAS CORP Needs Review
01/12/2021 RLEIGH1 UTILITY CLEARANCES EL PASO NATURAL GAS Needs Review
01/12/2021 RLEIGH1 UTILITY CLEARANCES KINDER MORGAN ENERGY Needs Review