Plan Number: T20PI00023
Parcel: Unknown

Review Status: Completed

Review Details: PIA - SUBMITTAL

Plan Number - T20PI00023
Review Name: PIA - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2021 GARY WITTWER DOT LANDSCAPE REVIEW Reqs Change DTM Landscape:

1. Add the following notes to the plans and comply with all requirements listed in notes.

City of Tucson, Department of Transportation and Mobility
Requirements for placement of Private Irrigation Facilities Roadway Crossings within the Public Rights-of-Way

1. Private irrigation facilities roadway crossings will only be permitted in residential roadways and NOT permitted in arterial or collector roadways.
2. Lateral lines under constant pressure shall not be permitted in the public rights-of-way.
3. The HOA/Owner will register private irrigation facilities placed in the public rights-of-way with Arizona 811and become an Arizona 811 Blue Stake Inc. member.
4. Minimize the number of roadway crossings.
5. Sleeves must be in a recorded easement (easement width is dependent on what is needed for installation and/or repairs). To the extent possible, the easements should be created at the time of development/platting.
6. Irrigation lines shall be placed in ductile iron sleeves.
7. Sleeve should extend beyond the right-of-way (into private property), unless otherwise approved by TDOT.
8. HDPE continuous line (no joints under the pavement)
9. Irrigation lines shall have a minimum of thirty (30) inches of cover.
10. Detectable marking tape shall be installed.
11. Curb shall be marked/stamped with "IS" (Irrigation System) and/or placard at back of curb.


Thank you,

David

David Marhefka
Landscape Architect
City of Tucson
Department of Transportation and Mobility
(o) 520-837-6618
(m) 520-403-5074
01/06/2021 RLEIGH1 UTILITY CLEARANCES COT STREETS DIVISION Needs Review
01/06/2021 ZELIN CANCHOLA DOT TRAFFIC REVIEW Approved
01/06/2021 RICHARD LEIGH PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Completed Please submit utility notification confirmation for the utility companies listed on the PIA utility notification list. The list can be found at: https://www.tucsonaz.gov/tdot/private-improvement-agreement-guidelines
01/06/2021 JIM FEMLING DOT STREET MAINTENANCE REVIEW Approved
01/06/2021 ERNIE ENCINAS DOT_ELEC REVIEW Approved
01/06/2021 RICHARD LEIGH DOT ENGINEERING REVIEW Reqs Change January 4, 2020

SUBJECT: La Estancia Phase II, Parcel 5 Paving Plans

PROJECT REVIEWER: Richard Leigh, DTM Eng. Review

RESUBMITTAL REQUIRED: DTM Permit Review Section has reviewed the subject PIA paving plan and does not recommend approval at this time. The following comments need to be addressed and plans revised prior to resubmittal. Please include a response letter addressing the following comments.


1. Add the plan number "I-2020-025" in the title block of each sheet.

2. Add PIA activity number "T20PI00023" on coversheet.

3. Sheet 2: Paving Note 5 to indicate that the asphaltic concrete shall conform to PAG's Replacement Specification for Section 406 Asphaltic Concrete, dated December 12, 2019.

4. Sheet 2 through 11: Use current DTM title blocks. See Engineering Plan Template at: https://www.tucsonaz.gov/files/transportation/Engineering_Plan_Templates_Dec_2019.pdf

5. Sheets 3: Revise scupper detail to indicate placement of barricade railing along the back of the scupper.

6. Sheets 3: Verify the data provided in the Scupper Information Table, revise as necessary.

7. Sheets 4: Curb access ramps will have to be provided at the intersection of Via De Ayante and Camino Vista Azul. Refer to COT TSM Section 10-01.3.3.E

8. Sheets 5: Curb access ramps will have to be provided at the intersection of Via De Ayante and Camino Cardal. Refer to COT TSM Section 10-01.3.3.E

9. Sheets 9: Curb access ramps will have to be provided at the intersection of Caminito La Piscins and Camino Cardal. Refer to COT TSM Section 10-01.3.3.E

10. Refer to redline drawings for additional comments and comment details.

If you have any questions, I can be reached at 520-237-8692 or emailed at Richard.Leigh@tucsonaz.gov.
01/06/2021 RICHARD LEIGH PIA COORDINATOR OUT TO CUSTOMER Completed Please submit utility notification confirmation for the utility companies listed on the PIA utility notification list. The list can be found at: https://www.tucsonaz.gov/tdot/private-improvement-agreement-guidelines
01/06/2021 RLEIGH1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Needs Review
01/06/2021 RLEIGH1 UTILITY CLEARANCES PC WASTEWATER MGMT Needs Review
01/06/2021 RLEIGH1 UTILITY CLEARANCES QUEST COMMUNICATION Needs Review
01/06/2021 RLEIGH1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Needs Review
01/06/2021 RLEIGH1 UTILITY CLEARANCES COX COMMUNICATION Needs Review
01/06/2021 RLEIGH1 UTILITY CLEARANCES SOUTHWEST GAS CORP Needs Review
01/06/2021 RLEIGH1 UTILITY CLEARANCES EL PASO NATURAL GAS Needs Review
01/06/2021 RLEIGH1 UTILITY CLEARANCES KINDER MORGAN ENERGY Needs Review