Address:
5148 E 22ND ST

Review Status: Completed

Review Details: PIA - SUBMITTAL

Plan Number - T20PI00012
Review Name: PIA - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/13/2020 JIM FEMLING DOT STREET MAINTENANCE REVIEW Approved
08/13/2020 RLEIGH1 UTILITY CLEARANCES COT STREETS DIVISION Completed
08/13/2020 ERNIE ENCINAS DOT_ELEC REVIEW Reqs Change City of Tucson DTM, Traffic Maintenance - Electric Shop has reviewed the Offsite Improvement Plans for "Thoroughbred Nissan".
Please see attachment for comments provided on Page 2 of 4, Offsite Improvement Plan for Thoroughbred Nissan.
Comments are as follows:
Site Plan Keynote for "Existing Street Light to remain".
Site Plan Keynote for "Existing Junction Box to remain".
Site Plan Keynote for "Relocate Street Light Junction Box out of ramp area. Electrical installation shall meet City of Tucson
standard specifications and details and will be coordinated with Traffic Maintenance Inspector".
Also attached is a signed UTILITY PLAN RECEIPT.
Please let us know if there are any questions or concerns.
Gabriel Rascon
Traffic Maintenance Superintendent
Department of Transportation and Mobility
Mobile: (520) 400-7656
Gabriel.Rascon@tucsonaz.gov
08/13/2020 RLEIGH1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Completed
08/13/2020 RLEIGH1 UTILITY CLEARANCES PC WASTEWATER MGMT Completed
08/13/2020 RLEIGH1 UTILITY CLEARANCES QUEST COMMUNICATION Needs Review
08/13/2020 RLEIGH1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Needs Review
08/13/2020 RLEIGH1 UTILITY CLEARANCES COX COMMUNICATION Completed
08/13/2020 RLEIGH1 UTILITY CLEARANCES SOUTHWEST GAS CORP Needs Review
08/13/2020 RLEIGH1 UTILITY CLEARANCES EL PASO NATURAL GAS Completed
08/13/2020 RLEIGH1 UTILITY CLEARANCES KINDER MORGAN ENERGY Completed
08/20/2020 ZELIN CANCHOLA DOT TRAFFIC REVIEW Approved
08/20/2020 RICHARD LEIGH PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Completed
08/20/2020 GARY WITTWER DOT LANDSCAPE REVIEW Approved
08/20/2020 RICHARD LEIGH PIA COORDINATOR OUT TO CUSTOMER Completed
08/20/2020 RICHARD LEIGH DOT ENGINEERING REVIEW Reqs Change August 20, 2020

SUBJECT: Offsite Improvements Plan for Thoroughbred Nissan

PROJECT REVIEWER: Richard Leigh, TDOT, TDOT Eng. Review

RESUBMITTAL REQUIRED: TDOT Permit Review Section has reviewed the subject PIA paving plan and does not recommend approval at this time. The following comments need to be addressed and plans revised prior to resubmittal. Please include a response letter addressing the following comments and return redlined drawings with subsequent submittal.

1. Add the plan number "U-2020-010" in the title block of each sheet.

2. Add PIA activity number "T20PI00012" on coversheet.

3. Add Development Plan number on coversheet.

4. Sheet 2: Revise drawing to relocate bus pad west, from out in front the existing light pole.

5. Sheet 2: Revise drawing to indicate the final surface treatment of the area between the curb and sidewalk.

6. Sheet 3: Revise drawing to depict the sidewalk scuppers extending through curb, per SD 205.

7. Sheet 3: Provide a cross section of Rosemont Ave.

8. Sheet 3: Revise drawing to indicate the placement of a curb terminal section at Sta. 22+74.99, 23.83 LT.

9. Sheet 3: Revise drawing to indicate that the existing grade at the termination of the sidewalk will be adjusted to meet the top of new sidewalk.

If you have any questions, I can be reached at 520-237-8692 or emailed at Richard.Leigh@tucsonaz.gov.