Plan Number: T20PI00007
Parcel: Unknown

Address:
6255 E GRANT RD

Review Status: Completed

Review Details: PIA - SUBMITTAL

Plan Number - T20PI00007
Review Name: PIA - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/08/2020 JIM FEMLING DOT STREET MAINTENANCE REVIEW Approved No Comments
06/08/2020 ERNIE ENCINAS DOT_ELEC REVIEW Approved Hello Gabriel and Richard

Looking at the prints conduits (10) and (15) are being extended.
I assume that this means that the conduits crossing the streets remain intact (unchanged).
If they are not being removed, I have no change.
If they are being removed, I would like to bring them up to current standard.
The originals were 2-2" conduits, I would like to upgrade these to our current standard of 2- 4" conduits.

Thank You
Roger
06/08/2020 ZELIN CANCHOLA DOT TRAFFIC REVIEW Approv-Cond 1. - Sheet 1, Striping Notes 6 and 7: The final longitudinal and transverse markings in the public ROW should be Extruded, not Hot-Sprayed.

2. - Sheet 4, Signing Note 6: There is one sign in this project. It is regulatory, and as such, the sheeting type should be Type IV. The only regulatory signs we call for Type XI sheeting on are Stop signs, Yield signs, and overhead signs.

Greg Orsini, P.E.
Department of Transportation & Mobility
City of Tucson
(P) 520-837-6617
(C) 520-268-5036
Gregory.Orsini@tucsonaz.gov
06/10/2020 RICHARD LEIGH DOT ENGINEERING REVIEW Reqs Change SUBJECT: Offsite Improvements Plan for Costco Wholesale #407

PROJECT REVIEWER: Richard Leigh, TDOT, TDOT Eng. Review

RESUBMITTAL REQUIRED: TDOT Permit Review Section has reviewed the subject PIA paving plan and does not recommend approval at this time. The following comments need to be addressed and plans revised prior to resubmittal. Please include a response letter addressing the following comments and return redlined drawings with subsequent submittal.

1. Add the plan number "I-2020-009" in the title block of each sheet.

2. Add PIA activity number "T20PI00007" on cover sheet.

3. If applicable, add project's development plan on cover sheet.

4. Use latest TDOT engineering plan template for this plan set. The latest TDOT engineering plan template can be found at https://www.tucsonaz.gov/tdot/engineering. Additionally, include Record Document block.

5. Sheet 1: Add the City of Tucson Department of Transportation and Mobility Paving Notes. DTM notes can be found at https://www.tucsonaz.gov/tdot/private-improvement-agreement under PIA Guidelines and Forms.

6. Revise drawing to provide Type 1 curb access ramp (With Pedestrian Push Button Access Ramps) refer to PAG S.D. 207 sheet 4 of 10.

7. An easement will be required for the catch basin and storm drain condit if they are located on private property.

If you have any questions, I can be reached at 520-237-8692 or emailed at Richard.Leigh@tucsonaz.gov.
06/10/2020 RLEIGH1 UTILITY CLEARANCES COT STREETS DIVISION Needs Review Please submit utility notification receipts. A list of utility companies that need to be notified of the proposed improvements in the public right-of-way at the following link.

https://www.tucsonaz.gov/files/transportation/UTLAWAREMEM_rev2019Mar27z.pdf
06/10/2020 RLEIGH1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Needs Review Please submit utility notification receipts. A list of utility companies that need to be notified of the proposed improvements in the public right-of-way at the following link.

https://www.tucsonaz.gov/files/transportation/UTLAWAREMEM_rev2019Mar27z.pdf
06/10/2020 RLEIGH1 UTILITY CLEARANCES PC WASTEWATER MGMT Needs Review Please submit utility notification receipts. A list of utility companies that need to be notified of the proposed improvements in the public right-of-way at the following link.

https://www.tucsonaz.gov/files/transportation/UTLAWAREMEM_rev2019Mar27z.pdf
06/10/2020 RLEIGH1 UTILITY CLEARANCES QUEST COMMUNICATION Needs Review Please submit utility notification receipts. A list of utility companies that need to be notified of the proposed improvements in the public right-of-way at the following link.

https://www.tucsonaz.gov/files/transportation/UTLAWAREMEM_rev2019Mar27z.pdf
06/10/2020 RLEIGH1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Needs Review Please submit utility notification receipts. A list of utility companies that need to be notified of the proposed improvements in the public right-of-way at the following link.

https://www.tucsonaz.gov/files/transportation/UTLAWAREMEM_rev2019Mar27z.pdf
06/10/2020 RLEIGH1 UTILITY CLEARANCES COX COMMUNICATION Needs Review Please submit utility notification receipts. A list of utility companies that need to be notified of the proposed improvements in the public right-of-way at the following link.

https://www.tucsonaz.gov/files/transportation/UTLAWAREMEM_rev2019Mar27z.pdf
06/10/2020 RLEIGH1 UTILITY CLEARANCES SOUTHWEST GAS CORP Needs Review Please submit utility notification receipts. A list of utility companies that need to be notified of the proposed improvements in the public right-of-way at the following link.

https://www.tucsonaz.gov/files/transportation/UTLAWAREMEM_rev2019Mar27z.pdf
06/10/2020 RLEIGH1 UTILITY CLEARANCES EL PASO NATURAL GAS Needs Review Please submit utility notification receipts. A list of utility companies that need to be notified of the proposed improvements in the public right-of-way at the following link.

https://www.tucsonaz.gov/files/transportation/UTLAWAREMEM_rev2019Mar27z.pdf
06/10/2020 RLEIGH1 UTILITY CLEARANCES KINDER MORGAN ENERGY Needs Review Please submit utility notification receipts. A list of utility companies that need to be notified of the proposed improvements in the public right-of-way at the following link.

https://www.tucsonaz.gov/files/transportation/UTLAWAREMEM_rev2019Mar27z.pdf
12/09/2020 RICHARD LEIGH PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Completed Please submit utility notification receipts. A list of utility companies that need to be notified of the proposed improvements in the public right-of-way at the following link.

https://www.tucsonaz.gov/files/transportation/UTLAWAREMEM_rev2019Mar27z.pdf
12/09/2020 RICHARD LEIGH PIA COORDINATOR OUT TO CUSTOMER Completed Please submit utility notification receipts. A list of utility companies that need to be notified of the proposed improvements in the public right-of-way at the following link.

https://www.tucsonaz.gov/files/transportation/UTLAWAREMEM_rev2019Mar27z.pdf