Plan Review Detail
Review Status: Completed
Review Details: PIA - SUBMITTAL
Plan Number - T20PI00007
Review Name: PIA - SUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/08/2020 | JIM FEMLING | DOT STREET MAINTENANCE | REVIEW | Approved | No Comments |
| 06/08/2020 | ERNIE ENCINAS | DOT_ELEC | REVIEW | Approved | Hello Gabriel and Richard Looking at the prints conduits (10) and (15) are being extended. I assume that this means that the conduits crossing the streets remain intact (unchanged). If they are not being removed, I have no change. If they are being removed, I would like to bring them up to current standard. The originals were 2-2" conduits, I would like to upgrade these to our current standard of 2- 4" conduits. Thank You Roger |
| 06/08/2020 | ZELIN CANCHOLA | DOT TRAFFIC | REVIEW | Approv-Cond | 1. - Sheet 1, Striping Notes 6 and 7: The final longitudinal and transverse markings in the public ROW should be Extruded, not Hot-Sprayed. 2. - Sheet 4, Signing Note 6: There is one sign in this project. It is regulatory, and as such, the sheeting type should be Type IV. The only regulatory signs we call for Type XI sheeting on are Stop signs, Yield signs, and overhead signs. Greg Orsini, P.E. Department of Transportation & Mobility City of Tucson (P) 520-837-6617 (C) 520-268-5036 Gregory.Orsini@tucsonaz.gov |
| 06/10/2020 | RICHARD LEIGH | DOT ENGINEERING | REVIEW | Reqs Change | SUBJECT: Offsite Improvements Plan for Costco Wholesale #407 PROJECT REVIEWER: Richard Leigh, TDOT, TDOT Eng. Review RESUBMITTAL REQUIRED: TDOT Permit Review Section has reviewed the subject PIA paving plan and does not recommend approval at this time. The following comments need to be addressed and plans revised prior to resubmittal. Please include a response letter addressing the following comments and return redlined drawings with subsequent submittal. 1. Add the plan number "I-2020-009" in the title block of each sheet. 2. Add PIA activity number "T20PI00007" on cover sheet. 3. If applicable, add project's development plan on cover sheet. 4. Use latest TDOT engineering plan template for this plan set. The latest TDOT engineering plan template can be found at https://www.tucsonaz.gov/tdot/engineering. Additionally, include Record Document block. 5. Sheet 1: Add the City of Tucson Department of Transportation and Mobility Paving Notes. DTM notes can be found at https://www.tucsonaz.gov/tdot/private-improvement-agreement under PIA Guidelines and Forms. 6. Revise drawing to provide Type 1 curb access ramp (With Pedestrian Push Button Access Ramps) refer to PAG S.D. 207 sheet 4 of 10. 7. An easement will be required for the catch basin and storm drain condit if they are located on private property. If you have any questions, I can be reached at 520-237-8692 or emailed at Richard.Leigh@tucsonaz.gov. |
| 06/10/2020 | RLEIGH1 | UTILITY CLEARANCES | COT STREETS DIVISION | Needs Review | Please submit utility notification receipts. A list of utility companies that need to be notified of the proposed improvements in the public right-of-way at the following link. https://www.tucsonaz.gov/files/transportation/UTLAWAREMEM_rev2019Mar27z.pdf |
| 06/10/2020 | RLEIGH1 | UTILITY CLEARANCES | COT WATER NEW DEVELOPMENT | Needs Review | Please submit utility notification receipts. A list of utility companies that need to be notified of the proposed improvements in the public right-of-way at the following link. https://www.tucsonaz.gov/files/transportation/UTLAWAREMEM_rev2019Mar27z.pdf |
| 06/10/2020 | RLEIGH1 | UTILITY CLEARANCES | PC WASTEWATER MGMT | Needs Review | Please submit utility notification receipts. A list of utility companies that need to be notified of the proposed improvements in the public right-of-way at the following link. https://www.tucsonaz.gov/files/transportation/UTLAWAREMEM_rev2019Mar27z.pdf |
| 06/10/2020 | RLEIGH1 | UTILITY CLEARANCES | QUEST COMMUNICATION | Needs Review | Please submit utility notification receipts. A list of utility companies that need to be notified of the proposed improvements in the public right-of-way at the following link. https://www.tucsonaz.gov/files/transportation/UTLAWAREMEM_rev2019Mar27z.pdf |
| 06/10/2020 | RLEIGH1 | UTILITY CLEARANCES | TUCSON ELECTRIC POWER CO | Needs Review | Please submit utility notification receipts. A list of utility companies that need to be notified of the proposed improvements in the public right-of-way at the following link. https://www.tucsonaz.gov/files/transportation/UTLAWAREMEM_rev2019Mar27z.pdf |
| 06/10/2020 | RLEIGH1 | UTILITY CLEARANCES | COX COMMUNICATION | Needs Review | Please submit utility notification receipts. A list of utility companies that need to be notified of the proposed improvements in the public right-of-way at the following link. https://www.tucsonaz.gov/files/transportation/UTLAWAREMEM_rev2019Mar27z.pdf |
| 06/10/2020 | RLEIGH1 | UTILITY CLEARANCES | SOUTHWEST GAS CORP | Needs Review | Please submit utility notification receipts. A list of utility companies that need to be notified of the proposed improvements in the public right-of-way at the following link. https://www.tucsonaz.gov/files/transportation/UTLAWAREMEM_rev2019Mar27z.pdf |
| 06/10/2020 | RLEIGH1 | UTILITY CLEARANCES | EL PASO NATURAL GAS | Needs Review | Please submit utility notification receipts. A list of utility companies that need to be notified of the proposed improvements in the public right-of-way at the following link. https://www.tucsonaz.gov/files/transportation/UTLAWAREMEM_rev2019Mar27z.pdf |
| 06/10/2020 | RLEIGH1 | UTILITY CLEARANCES | KINDER MORGAN ENERGY | Needs Review | Please submit utility notification receipts. A list of utility companies that need to be notified of the proposed improvements in the public right-of-way at the following link. https://www.tucsonaz.gov/files/transportation/UTLAWAREMEM_rev2019Mar27z.pdf |
| 12/09/2020 | RICHARD LEIGH | PIA COORDINATOR | CUSTOMER CALLED; PLANS @ AMBASSSADOR | Completed | Please submit utility notification receipts. A list of utility companies that need to be notified of the proposed improvements in the public right-of-way at the following link. https://www.tucsonaz.gov/files/transportation/UTLAWAREMEM_rev2019Mar27z.pdf |
| 12/09/2020 | RICHARD LEIGH | PIA COORDINATOR | OUT TO CUSTOMER | Completed | Please submit utility notification receipts. A list of utility companies that need to be notified of the proposed improvements in the public right-of-way at the following link. https://www.tucsonaz.gov/files/transportation/UTLAWAREMEM_rev2019Mar27z.pdf |