Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Plan Number: T20PI00004
Parcel: Unknown

Address: Unknown

Review Status: Completed

Review Details: PIA - SUBMITTAL

Plan Number - T20PI00004
Review Name: PIA - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2020 RLEIGH1 UTILITY CLEARANCES COT STREETS DIVISION Completed
04/21/2020 ERNIE ENCINAS DOT_ELEC REVIEW Approved
04/21/2020 RLEIGH1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Completed
04/21/2020 RLEIGH1 UTILITY CLEARANCES PC WASTEWATER MGMT Completed
04/21/2020 RLEIGH1 UTILITY CLEARANCES QUEST COMMUNICATION Completed
04/21/2020 RLEIGH1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Completed
04/21/2020 RLEIGH1 UTILITY CLEARANCES COX COMMUNICATION Completed
04/21/2020 RLEIGH1 UTILITY CLEARANCES SOUTHWEST GAS CORP Completed
04/21/2020 RLEIGH1 UTILITY CLEARANCES EL PASO NATURAL GAS Completed
04/21/2020 RLEIGH1 UTILITY CLEARANCES KINDER MORGAN ENERGY Completed
05/15/2020 GARY WITTWER DOT LANDSCAPE REVIEW Reqs Change David Marhefka
Landscape Architect
City of Tucson
Department of Transportation and Mobility
(o) 520-837-6618
(m) 520-403-5074


Please update the Standard Notes for Planting in the ROW

City of Tucson
Department of Transportation & Mobility
Standard Notes for Planting in Right of Way

1. It is the owner's responsibility to keep the Sight Visibility Triangles (SVT), and the pedestrian access area clear of vegetation at all times, per Unified Development Code Technical Standards Manual section 10.
2. It is the owner responsibility to keep a 5' wide by 7' tall clear pedestrian access open across the entire property.
3. It is the owner responsible to keep vegetation from growing past the curb line clear, and keep a 15' high clear zone over the travel lane.
4. Final plant locations must be in compliance with all utility setback requirements.
5. The owner understands that if the City of Tucson Department of Transportation & Mobility or any utility company needs to work within the ROW in the landscaped area, plants and irrigation may be destroyed without replacement or repair.
6. The owner takes full liability for this landscape and irrigation, and any damage to roadway, sidewalk and utilities.
7. The only private irrigation equipment that is allowed within the ROW are lateral lines, tubing and emitters that are not under constant pressure. All other equipment must be on private property (excluding water meter).
8. Contractor to obtain a ROW permit prior to construction within the ROW.
05/15/2020 RICHARD LEIGH PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Completed
05/15/2020 ZELIN CANCHOLA DOT TRAFFIC REVIEW Reqs Change Blake Olofson
Blake.Olofson@tucsonaz.gov


1. Should the widening extend through the bus pullout? This would make it easier for transit vehicles to accelerate for the merge back into traffic.

2. I believe that the SW corner of the intersection should be reconstructed (redesigned?) so the new curb ramp on the NW corner lines up. This will likely require that the median in the side street (name?) be moved back to the west.


********************************************************************

Greg Orcini
Gregory.Orsini@tucsonaz.gov

Please see redline drawings
05/15/2020 RICHARD LEIGH PIA COORDINATOR OUT TO CUSTOMER Completed
05/15/2020 JIM FEMLING DOT STREET MAINTENANCE REVIEW Approved
05/15/2020 RICHARD LEIGH DOT ENGINEERING REVIEW Reqs Change May 15, 2020

SUBJECT: Offsite Improvements Plan for The Bridges B-III

PROJECT REVIEWER: Richard Leigh, TDOT, TDOT Eng. Review

RESUBMITTAL REQUIRED: TDOT Permit Review Section has reviewed the subject PIA paving plan and does not recommend approval at this time. The following comments need to be addressed and plans revised prior to resubmittal. Please include a response letter addressing the following comments and return redlined drawings with subsequent submittal.

1. Add the plan number "U-2020-009" in the title block of each sheet.

2. Add PIA activity number "T20PI00004" on cover sheet.

3. Sheet 1: Revise Paving + Grading Note #3 to indicate the use of City of Tucson Mix #2.

4. Sheet 2: Revise drawing to indicate the placement of concrete sidewalk along the property frontage Per PAG Standard Detail 200 pursuant to COT Technical Standard Manual Section 10-01.4.1.C.

5. Revise drawing to indicate placement of sidewalk along the entire frontage of the property. Sidewalk needs to be provided south of the proposed spine road pursuant to COT Technical Standard Section 10-01-3.3.A.

6. Sheet 2: A public access easement will be required for the section of sidewalk along Kino Blvd that encroaches onto private property. Depict easement and label with redecoration information. Contact the City of Tucson Department of Transportation Real Estate division for details.

7. Sheet 2: An area must be dedicated to the City or an easement provided to the City for the Light pole relocated onto private property. Depict area and label with recordation information. Contact the City of Tucson Department of Transportation Real Estate division for details.

8. Sheet 2: Provide all information and details of all landscaping proposed within the public rights-of-way. This document should stand alone and not refer to other documents for details.

9. Sheet 2: Provide complete details for the curb return and access ramp on the south side of proposed driveway. This document should stand alone and not refer to other documents for details.

10. Sheet 2: Redesign curb return on the sothe side of the proposed sine road so the curb access ramp will be in line with ramp opposite to it, pursuant to COT T.S.M. 10-01.3.3.E.

11. Sheet 2: Revise keynote 11 to indicate curb access ramp type.

12. Sheet 4, Detail B: Indicate that the pavement section must be matched if an existing thicker pavement section is encountered during construction.

13. Sheet 4, Detail B: TDOT requires a terminal blend binder for pavement surface courses. Indicate this requirement on detail.

If you have any questions, I can be reached at 837-6647 or emailed at Richard.Leigh@tucsonaz.gov.

Richard Leigh
Sr. Engineering Associate
Department of Transportation and Mobility
520-837-6647 Office
520-237-8692 Cell