Permit Number: T20OT00608
Parcel: 117141600

Address:
415 S MEYER AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T20OT00608
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/12/2021 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment; General: A previous Certificate of Occupancy was not located in our records. In order to receive a Certificate of Occupancy, a registered architect is required to provide a site plan that indicates the building location.
2. Previous Comment; General: The registered architect is required to provide a building plan. In addition, a Code Analysis is required on this sheet, indicating the Occupancy Classification, Construction Type, Square Footage, if the building has an Automatic Sprinkler System, and the allowable Occupant Load.
3. General: The documents in this submittal were for a Fire Inspection, not a C of O.